ABB SACE Emax 2 E2.2/E4.2/E6.2 fixed part of withdrawable circuit breaker: installation, wiring, fixing and operating positions.
This document covers the fixed part of the withdrawable circuit breaker for SACE Emax 2 frames E2.2, E4.2 and E6.2, including installation in ReliaGear LV SG switchboards. It shows fixing methods, wiring examples, label rotation before inserting the mobile part, and the disconnect, test and connected positions.
It also describes precautions for withdrawing the moving part and gives an example of lockable guides for E2.2 III. The document is multilingual and includes warnings, diagrams and installation notes.
| Fixing screw maximum diameter | 4.3 mm (0.17 in) |
|---|---|
| Fixing screw tightening torque | 8.6 Nm (76 lb-in) |
| Maximum cable outer diameter | 3.3 mm (0.13 in) |
| Lockable guides (E2.2 III) | max. 3+3, Ø 8 mm (0.31 in) |
It can operate only when the PUSH BEFORE OPERATE button is not pressed and the circuit breaker is in one of the disconnect, test or connected positions.
Rotate the label by 90° before inserting the mobile part.
The fixing screws require a tightening torque of 8.6 Nm (76 lb-in).
Both guides on the fixed part must travel the same extent so the moving part remains parallel to the fixed part.