ABB M2SE Low Voltage Smoke Extraction Motor Additional Manual

Additional manual for ABB M2SE low voltage smoke extraction motors covering validity, maintenance inspection, and additional instructions.


ABB M2SE Low Voltage Smoke Extraction Motor Additional Manual - cover page
Brand
ABB
Category
Motor
Document type
User Manual
Language
Chinese
Pages
8
File format
PDF
File size
411 KB
Published
17 November, 2026
Updated
17 November, 2026
MD5 checksum
556E1520CF14BA30ABE6CD7FBF7F8EED

About this manual

ABB M2SE low voltage smoke extraction motors are intended for daily comfort ventilation and smoke extraction during fire. This additional manual supplements the standard low voltage motor manual and gives inspection and maintenance guidance for normal and emergency ventilation operation.

Key points include bearing service life over 20,000 hours, inspection intervals of 12 months for normal ventilation and 3 months for emergency ventilation, and operating limits of 300°C for 60 minutes or 250°C for 120 minutes. It also states that rewinding is not allowed and that the motor must be replaced after high-temperature emergency operation. This manual is written in Chinese.

What's inside

  • Validity
  • Maintenance inspection
  • Normal ventilation only
  • Emergency ventilation only
  • Additional instructions
  • Smoke extraction motors in variable speed operation

Specifications

Motor seriesM2SE
Operating temperature and duration300°C for 60 min or 250°C for 120 min
Maximum ambient temperature with frequency converter40°C
Bearing service lifetime L10hMust exceed 20,000 hours
Insulation resistanceHigher than 10 MΩ at 25°C with 500 V DC
FanEquipped with a fan as standard; optional without fan

Frequently asked questions

Which ABB motor series does this additional manual cover?

It applies to ABB M2SE smoke extraction motors.

What temperature and duration can the motors operate at?

They can operate at 300°C for 60 minutes or 250°C for 120 minutes.

How often should the installation be inspected for normal ventilation?

At least every 12 months.

How often should the installation be inspected for emergency ventilation only?

At least every three months.