Additional manual for ABB M2SE low voltage smoke extraction motors covering validity, maintenance inspection, and additional instructions.
ABB M2SE low voltage smoke extraction motors are intended for daily comfort ventilation and smoke extraction during fire. This additional manual supplements the standard low voltage motor manual and gives inspection and maintenance guidance for normal and emergency ventilation operation.
Key points include bearing service life over 20,000 hours, inspection intervals of 12 months for normal ventilation and 3 months for emergency ventilation, and operating limits of 300°C for 60 minutes or 250°C for 120 minutes. It also states that rewinding is not allowed and that the motor must be replaced after high-temperature emergency operation. This manual is written in Chinese.
| Motor series | M2SE |
|---|---|
| Operating temperature and duration | 300°C for 60 min or 250°C for 120 min |
| Maximum ambient temperature with frequency converter | 40°C |
| Bearing service lifetime L10h | Must exceed 20,000 hours |
| Insulation resistance | Higher than 10 MΩ at 25°C with 500 V DC |
| Fan | Equipped with a fan as standard; optional without fan |
It applies to ABB M2SE smoke extraction motors.
They can operate at 300°C for 60 minutes or 250°C for 120 minutes.
At least every 12 months.
At least every three months.