ABB ACS310 Drive Short Form User's Manual

Short form user manual for ABB ACS310 general purpose drives covering installation, electrical connections, start-up, and basic I/O control.


ABB ACS310 Drive Short Form User's Manual - cover page
Brand
ABB
Category
inverter
Document type
User Manual
Language
English
Pages
50
File format
PDF
File size
5.2 MB
Published
20 November, 2026
Updated
20 November, 2026
Model
ACS310
MD5 checksum
582AD047D1627D7D96985FDAF5D0251F

About this manual

This short form user's manual provides the basic information needed for installing and commissioning the ABB ACS310 drive. It applies to firmware version 4.050 or later and references the full user's manual for detailed technical data, parameters, fault tracing, and maintenance.

The manual covers safety instructions, hardware description with power and control interfaces, mechanical installation (including cooling clearances), electrical installation (power and control cables, IT/corner-grounded systems), start-up and control via I/O, a short parameter view, and technical data such as ratings, fuses, and UL checklist.

What's inside

  • Safety
  • Hardware description
  • Mechanical installation
  • Electrical installation
  • Start-up and control with I/O
  • Actual signals and parameters in the short view
  • Technical data
  • Further information

Specifications

Input voltage range200–240 V AC (1-phase/3-phase) or 380–480 V AC (3-phase)
Output current rating example9.7 A (09A7)
Firmware applicabilityVersion 4.050 or later
Cooling free space75 mm (3 in) above and below
Maximum charging cyclesTwo per minute, 15,000 total

Frequently asked questions

What firmware version does this manual apply to?

This manual applies to ACS310 drive firmware version 4.050 or later.

What is the required cooling clearance for the drive?

The drive requires 75 mm (3 in) of free space above and below for cooling.

How should the internal EMC filter be configured for an IT (ungrounded) system?

Disconnect the internal EMC filter when installing the drive on an IT system to avoid connecting the system to ground potential through the filter capacitors.

What is the maximum number of power-up charging cycles allowed?

A maximum of two charging cycles per minute and 15,000 total charging cycles are allowed.