ABB Type 76H DC Overcurrent Relay Descriptive Bulletin

ABB Type 76H DC Overcurrent Relay descriptive bulletin covers applications, wiring diagrams, specifications, and ordering information.


ABB Type 76H DC Overcurrent Relay Descriptive Bulletin - cover page
Brand
ABB
Category
RELAY
Document type
Product Leaflet
Language
English
Pages
3
File format
PDF
File size
389 KB
Published
22 November, 2026
Updated
22 November, 2026
MD5 checksum
0C714797F9A006E56700C8D57F445CF0

About this manual

The ABB Type 76H DC Overcurrent Relay is a DC millivolt relay used with a shunt to provide instantaneous overcurrent protection. The bulletin lists typical applications in rectifier, feeder, and tie breakers in mining traction systems and industrial DC distribution systems.

This descriptive bulletin gives features, wiring diagrams, pickup and control power data, output ratings, operating time, and ordering references. It also describes an optional built-in calibrated test circuit and the use of standard #14 uncalibrated leads with existing 50 or 100 mv shunts.

What's inside

  • Features
  • Application
  • Pickup
  • Operating Time
  • Control Power
  • Output Rating
  • How To Specify
  • How To Order
  • Further Information

Specifications

Pickup taps10 taps, switch selected
Pickup range10-100 mVdc or 20-200 mVdc
Vernier adjustmentContinuous adjustment from tap value to next higher tap
Burden1000 ohms load on shunt
Control power120 Vac or 240 Vac
Operating timeVirtually instantaneous
Output circuit1 contact, which opens on overcurrent
Output ratingOpening contact, 325 Vdc
Operating temperatureMinus 20° to Plus 70°C
Dielectric strength1500V RMS for 1 minute

Frequently asked questions

What is the ABB Type 76H DC Overcurrent Relay used for?

It is used with a shunt to provide instantaneous overcurrent protection. Typical applications include rectifier, feeder, and tie breakers in mining traction systems and industrial DC distribution systems.

Can the ABB Type 76H use standard shunts and uncalibrated leads?

Yes. The bulletin says standard #14 uncalibrated leads may be used with existing 50 or 100 mv shunts.

What control power does the ABB Type 76H require?

Unidirectional tripping models operate from 120 to 240 Vac control-power transformers. The catalog table lists 120 Vac or 240 Vac.

Does the ABB Type 76H include a test function?

An optional built-in calibrated test circuit allows an operator to verify that the relay is operating within its calibration.

Download PDF (389 KB)