Thomson BCM 1220 Battery Charger Service Manual

This document provides the installation, operation, and maintenance manual for the BCM 1220 automatic battery charger. It includes installation requirements and precautions, as well as the working principle and adjustment methods for float and equalize charging.


Brand
THOMSON
Category
Battery Charger
Document type
Service Manual
Language
Chinese
Pages
7
File format
PDF
File size
176 KB
Updated
28 September, 2023
MD5 checksum
2DCF4A080084FCE82BDAE99A23BDF42E

About this manual

This manual explains how to install the BCM 1220 charger in a dry, ventilated location, connect it to a 120 VAC or 240 VAC, 15 A grounded supply, and observe safety precautions such as avoiding explosive gases and ensuring correct polarity. It also lists environmental limits, including a maximum ambient temperature of 104 °F (40 °C).

The charger supports float and equalize (均充) charging modes that are selected with a dedicated switch or optional APB‑1210 alarm/control module. Detailed procedures for adjusting float and equalize voltages, setting current limits, and using the optional alarm functions are provided. This manual is written in Chinese.

What's inside

  • Installation
  • Float and Equalize Charging Modes
  • Output Adjustment
  • Battery Disconnection
  • Electrical Connections
  • Optional APB 1210 Alarm/Control Module

Specifications

Input voltage120 VAC or 240 VAC, 50/60 Hz, 15 A
Maximum ambient temperature104 °F (40 °C)
Float voltage (12 V battery)12.8 VDC
Float voltage (24 V battery)25.6 VDC
Current limit setting100 % of name‑plate rating

Frequently asked questions

What input voltage should be used for the BCM 1220 charger?

Connect the charger to a 120 VAC or 240 VAC, 50/60 Hz supply that can provide at least 15 A with grounding.

How do I switch between float and equalize (均充) charging modes?

Use the “float/equalize” switch or the optional manual equalize regulator; the switch selects the desired mode.

How can I adjust the float voltage?

Connect a precise voltmeter in parallel with the battery, set the charger to the float position, wait for the voltage to stabilize, then turn the fine potentiometer clockwise to increase voltage or counter‑clockwise to decrease it.

What safety precautions are required when connecting the charger to a battery?

Ensure the correct polarity, disconnect any load before adjusting, keep sparks and flames away, and have only qualified personnel perform maintenance.

Download PDF (176 KB)