Dell Online Rack-Mountable UPS 2700W (Watts) User’s Guide
This is the Chinese user guide for the Dell online rack-mountable UPS rated 2700W, covering the 2700R Telco LV (K803N), 2700R Telco HV-US (H950N) and 2700R Telco HV (J728N) models plus the 2700R EBM (H967N) external battery module. It explains how the online double-conversion UPS with pure sine wave output protects servers, network equipment and workstations from power failures, sags, surges and line noise.
The guide walks through safety warnings, unpacking and rack mounting, installation of the UPS and EBM, initial startup, control panel and display operation, mode changes, output switch control, battery settings and self-tests, RS-232/USB communication ports, the optional Dell network management card, maintenance and battery replacement, specifications and troubleshooting. This manual is written in Chinese.
| UPS models | 2700R Telco LV (K803N) 120V, 2700R Telco HV-US (H950N) 208V, 2700R Telco HV (J728N) 230V, all 2700W |
|---|---|
| External battery module | 2700R EBM (H967N), 96 Vdc |
| Dimensions (W x H x D) | 438.0 x 171.5 x 433.0 mm (17.2" x 6.8" x 17.0"), 4U |
| UPS weight | 36.9 kg (81.4 lb) |
| EBM weight | 51.8 kg (114.2 lb) |
| Rated input voltage | 120V / 208V / 230V depending on model |
| Input voltage range | 82-144V auto-sensing (120V), 155-255V auto-sensing (208V), 160-286V auto-sensing (230V) |
| Nominal frequency | 50/60 Hz auto-sensing, +/-3 Hz |
| Efficiency (normal mode) | >95% |
| Output power rating | 2700W |
| Output voltage waveform | Sine wave |
| Operating temperature | 0 to 40 C up to 1,500 m; 0 to 35 C above 1,500 m |
| Storage/transport temperature | -15 C to 60 C (5 F to 140 F) |
| Relative humidity | 0-95% non-condensing |
| Operating altitude | Up to 3,048 m (0-10,000 ft) |
| Audible noise | Below 55 dBA in online/bypass mode (under 75% load) |
| Safety compliance | UL 1778 4th edition; CSA C22.2, No. 107.3; IEC/EN 62040-1-1; IEC/EN 60950-1 |
The 2700W UPS can be connected to at most one external battery module (EBM).
It has two standard communication ports, a USB port and a DB-9 serial port.
0 to 40 C at altitudes up to 1,500 m, and 0 to 35 C above 1,500 m.
A battery start function lets the UPS supply power even without utility power.