The EA04A is a generator automatic voltage regulator for self-excited brushless generators. It can directly replace Basler *VR63-4, VR63-4A and is compatible with Marathon SE100A regulators. If the AVR needs to be grid-connected, it can be used with the Kutai EP200 grid-connected module.
Kutai EA04A is an automatic voltage regulator for self-excited brushless generators. The manual covers technical specifications, wiring, V/Hz automatic shutdown frequency selection, over-excitation shutdown, startup procedure, stability adjustment, and troubleshooting.
It can directly replace Basler VR63-4 and VR63-4A and is compatible with the Marathon SE100A regulator. If grid connection is required, it can be used with the Kutai EP200 grid-connection module. This manual is written in Chinese.
| Sensing voltage input (50 Hz system) | 90 132 Vac |
|---|---|
| Sensing voltage input (60 Hz system) | 171 264 Vac |
| Sensing frequency | 45/65 Hz |
| Power input voltage | 90 240 Vac |
| Power input frequency | 45/65 Hz |
| Field output voltage (max, 120 Vac input) | 最大 32 Vdc @ 电源输入 120 Vac |
| Field output voltage (max, 240 Vac input) | 最大 63 Vdc @ 电源输入 240 Vac |
| Field current | 连续 4A,非连续为 60 秒内 7A |
| Field resistance | 最小 15 Ω、最大 100 Ω |
| Voltage temperature drift | -40 至+70 ˚C,小于 3% |
| Fuse | 5 x 20mm S505-5A / 250V 慢熔型 |
| Operating temperature | -40 至+60 ˚C |
| Storage temperature | -40 至+85 ˚C |
| External voltage adjustment | 最大 +/- 15% @ 1 KΩ 1 watt 电位器 |
| Regulation accuracy | 小于 +/- 1% (频率变动在 4%内) |
| Residual voltage for build-up | 5 Vac 以上 |
| Dimensions | 100.0 (L) x 68.5 (W) x 33.0 (H) mm |
| Static power consumption | 最大 8 watts |
| Vibration (5-30 Hz) | 1.5 Gs @ 5 30 Hz |
| Vibration (30-500 Hz) | 5.0 Gs @ 30 500 Hz |
| EMI suppression | 内建电磁干扰滤波器 |
| Low-frequency protection corner (50 Hz system) | 拐点值为 45 Hz |
| Low-frequency protection corner (60 Hz system) | 拐点值为 55 Hz |
The specified fuse is 5 x 20mm S505-5A / 250V slow-blow.
Join the two leads marked Hz.
Cut the lead marked Hz.
The power input residual voltage must be above 5 Vac.