The F-Series Air Velocity Sensors User Guide describes the features and specifications of the F-Series Air Velocity Sensors.
This user guide covers Degree Controls F-Series air velocity and temperature sensors, including features, product specifications, wiring, mechanical details, mounting, communication, analog outputs, and sensor registers.
It also documents configurable F300, F400, and F500 models, input voltage and current requirements, velocity and temperature accuracy, environmental ratings, and installation guidance.
| Operating temperature | 0°C to 60°C (32°F to 140°F); -10°C to 60°C (14°F to 140°F) for F500/F550 |
|---|---|
| Storage temperature | -40°C to 105°C (-40°F to 221°F) |
| Air velocity range | Configurable, 0.15 m/s to 20 m/s (30 fpm to 4000 fpm) |
| Relative humidity | 5% to 95% |
| Acceptance angle | ±30° |
| Repeatability | ±1% of reading (under identical conditions) |
| Temperature accuracy | ±1°C |
| Response time | 400 ms |
| Airflow averaging time | Configurable (3 second default) |
| Start-up time | <10 s |
| Alarm output | Open drain, configurable trip point |
| Communication | I2C (400 kHz) or 3.3 V UART or BACnet MS/TP |
| Cable length | 2 m (6 ft.) |
| Housing construction | Polycarbonate (PC), UL94-V0 (head), UL94-HB (housing) |
| Environmental protection | IP65 electronics, including conformal coated sensing element |
| Air velocity accuracy (0.15 to 1.0 m/s) | ±(1% of reading + 0.05 m/s [10 fpm]) |
| Air velocity accuracy (0.5 to 10 m/s) | ±(4% of reading + 0.10 m/s [20 fpm]) |
| Air velocity accuracy (1.0 to 20 m/s) | ±(5% of reading + 0.15 m/s [30 fpm]) |
| F300 input voltage range | 4.5 – 15 VDC |
| F300 current consumption | <35 mA nominal |
| F400 input voltage range | 19 – 29 VDC |
| F400 current consumption | <15 mA nominal |
| F500/F500 BACnet input voltage range | 22 – 26 VAC/VDC |
| F500/F500 BACnet current consumption | <100 mA nominal |
The operating temperature range is 0°C to 60°C (32°F to 140°F), or -10°C to 60°C (14°F to 140°F) for F500 and F550 models.
The sensors support I2C (400 kHz), 3.3 V UART, or BACnet MS/TP communication.
The configurable air velocity range is 0.15 m/s to 20 m/s (30 fpm to 4000 fpm).
The temperature accuracy is ±1°C.