Degree Controls F-Series Air Velocity Sensors User Guide

The F-Series Air Velocity Sensors User Guide describes the features and specifications of the F-Series Air Velocity Sensors.


Degree Controls F-Series Air Velocity Sensors User Guide - cover page
Brand
DEGREE CONTROLS
Category
sensor
Document type
User Manual
Language
English
Pages
32
File format
PDF
File size
3.2 MB
Published
17 November, 2023
Updated
17 November, 2023
MD5 checksum
915316737B6D6A80A56951D8F4862E52

About this manual

This user guide covers Degree Controls F-Series air velocity and temperature sensors, including features, product specifications, wiring, mechanical details, mounting, communication, analog outputs, and sensor registers.

It also documents configurable F300, F400, and F500 models, input voltage and current requirements, velocity and temperature accuracy, environmental ratings, and installation guidance.

What's inside

  • General Information
  • Product Specifications
  • Wiring Information
  • Mechanical Information
  • Mounting and Positioning
  • Communication
  • Analog Outputs
  • Sensor Registers
  • Product Warranty
  • Hardware Configuration

Specifications

Operating temperature0°C to 60°C (32°F to 140°F); -10°C to 60°C (14°F to 140°F) for F500/F550
Storage temperature-40°C to 105°C (-40°F to 221°F)
Air velocity rangeConfigurable, 0.15 m/s to 20 m/s (30 fpm to 4000 fpm)
Relative humidity5% to 95%
Acceptance angle±30°
Repeatability±1% of reading (under identical conditions)
Temperature accuracy±1°C
Response time400 ms
Airflow averaging timeConfigurable (3 second default)
Start-up time<10 s
Alarm outputOpen drain, configurable trip point
CommunicationI2C (400 kHz) or 3.3 V UART or BACnet MS/TP
Cable length2 m (6 ft.)
Housing constructionPolycarbonate (PC), UL94-V0 (head), UL94-HB (housing)
Environmental protectionIP65 electronics, including conformal coated sensing element
Air velocity accuracy (0.15 to 1.0 m/s)±(1% of reading + 0.05 m/s [10 fpm])
Air velocity accuracy (0.5 to 10 m/s)±(4% of reading + 0.10 m/s [20 fpm])
Air velocity accuracy (1.0 to 20 m/s)±(5% of reading + 0.15 m/s [30 fpm])
F300 input voltage range4.5 – 15 VDC
F300 current consumption<35 mA nominal
F400 input voltage range19 – 29 VDC
F400 current consumption<15 mA nominal
F500/F500 BACnet input voltage range22 – 26 VAC/VDC
F500/F500 BACnet current consumption<100 mA nominal

Frequently asked questions

What is the operating temperature range of the F-Series sensors?

The operating temperature range is 0°C to 60°C (32°F to 140°F), or -10°C to 60°C (14°F to 140°F) for F500 and F550 models.

Which communication interfaces do the sensors support?

The sensors support I2C (400 kHz), 3.3 V UART, or BACnet MS/TP communication.

What air velocity range can be configured?

The configurable air velocity range is 0.15 m/s to 20 m/s (30 fpm to 4000 fpm).

What is the temperature accuracy?

The temperature accuracy is ±1°C.

Download PDF (3.2 MB)