The ETCR068H high voltage clamp type current sensor adopts the latest CT and shielding technology, clamp type hook design, no need to disconnect the tested line, the sensor can be hung on the line for testing, saving the operator's physical strength, safe and fast, ensuring high precision, high reliability and high stability of uninterrupted testing for many years.
ETCR 068H is a clamp-type current sensor for high- and low-voltage lines. It measures current, leakage current, ratio, high-order harmonic current, phase, energy, power, and power factor without disconnecting the conductor.
The manual covers safety precautions, specifications, operating principle, structure, and clamp configurations. For high-voltage work, the sensor is used with an insulating rod on insulated-sheath lines below AC 60 kV or bare conductors below 35 kV. This manual is written in Chinese.
| Function | Current, leakage current, ratio, high-order harmonic current, phase, energy, and power on high/low voltage lines |
|---|---|
| Battery compartment | Holds 4 x 1.5 V AAA alkaline dry batteries |
| Output method | Current sensing with coil tap output (S1, S2) |
| Clamp opening | φ68 mm |
| Range | 0.00 mA to 1000 A AC |
| Resolution | 0.01 mA AC |
| Accuracy | ±1.0% FS (segmented highest accuracy) |
| Turns ratio | 1:4000 |
| Phase error | ≤3° (50 Hz/60 Hz; 23 °C ±2 °C) |
| Reference load | 0–1 A ≤500 Ω; 0–10 A ≤50 Ω; 0–100 A ≤5 Ω; 0–1000 A ≤0.5 Ω |
| Output lead length | 10 cm |
| Electric field interference | About 10 mA when an external 100 A field is 10 mm away |
| Conductor position | Tested conductor at center of clamp |
| Current frequency | 45 Hz to 60 Hz |
| Frequency response | 10 Hz to 100 kHz |
| Line voltage | AC below 60 kV insulated-sheath lines or below 35 kV bare conductors |
| Dimensions | 218 mm × 135 mm × 60 mm |
| Weight | About 550 g |
| Operating conditions | -20 °C to 50 °C; below 80% RH |
| Storage conditions | -10 °C to 60 °C; below 70% RH |
| Structure | Clamp hook type |
| Insulation strength | AC 3700 V/rms (core to housing) |
| Safety compliance | IEC1010-1, IEC1010-2-032, pollution degree 2, CAT III (600 V) |
The battery compartment holds four 1.5 V AAA alkaline dry batteries.
The sensor measures AC current from 0.00 mA to 1000 A.
Clamp the live and neutral conductors together for single-phase leakage, or clamp all conductors of a three-phase circuit together.
It can be used on insulated-sheath lines below AC 60 kV or bare conductors below 35 kV.