The M-340Ir is a compact, high-accuracy, high-resolution leakage current tester that is suitable for field applications. It has a voltage test lead with a fuse and can be used with a variety of large-diameter leakage current converters to expand the range of use.
The M-340Ir is a compact Io/Ior clamp leakage current tester suited to field use, with high precision and high resolution for both Io and Ior down to 0.001 mA. It has fuse-protected voltage test leads and can be used with various large-diameter leakage converters to expand its application range.
The leaflet lists electrical and mechanical specifications, included accessories, optional LAD-800 and LAD-1100 leakage converters, and explains that leakage current Io consists of effective leakage current Ior and capacitive current Ioc. This manual is written in Chinese.
| Test functions | Effective leakage current Ior and leakage current Io |
|---|---|
| Ior test circuit | Single-phase 2-wire/3-wire; three-phase 3-wire delta |
| Ior resolution at 10 mA range | 0.001 mA |
| Ior accuracy at 10 mA range | ±1.0%rdg ±10dgt |
| Ior resolution at 100 mA range | 0.01 mA |
| Ior accuracy at 100 mA range | ±1.2%rdg ±10dgt |
| Io resolution at 10 mA range | 0.001 mA |
| Io accuracy at 10 mA range | ±1.0%rdg ±10dgt |
| Io resolution at 100 mA range | 0.01 mA |
| Io resolution at 1000 mA range | 0.1 mA |
| Input voltage measurement points | Single-phase V-N; three-phase R-T |
| Fuse-protected test leads | 3 m |
| Data hold | [DH] indicator lights and display data is held |
| Sampling speed | 2 times/second |
| Clamp opening diameter | φ40 mm |
| Test circuit voltage | AC 500 V or less |
| Operating temperature and humidity | 0 to 50°C, below 80% RH, non-condensing |
| Power supply | UM-4 ×3 |
| Dimensions and weight | 200 × 44 × 24 mm, about 210 g |
| Included accessories | Carrying case, UM-4 ×3, leads, instruction manual |
| Optional leakage converters | LAD-800, LAD-1100 |
| LAD-800 test range | AC 1000 A |
| LAD-800 CT ratio | 10:1, 100:1 |
| LAD-800 CT aperture | 800 mm × 74 mm |
| LAD-800 rated voltage | AC 600 V or less |
| LAD-800 weight | about 500 g |
| LAD-1100 low range | AC 3000 mA to 30 A |
| LAD-1100 high range | AC 30 A to 3000 A |
| LAD-1100 CT ratio | 10:1, 100:1 |
| LAD-1100 CT aperture | 128 mm × 108 mm |
| LAD-1100 rated voltage | AC 600 V or less |
| LAD-1100 weight | about 1800 g |
| Leakage current relation | Io = Ior + Ioc |
It measures effective leakage current Ior and leakage current Io.
The clamp opening diameter is φ40 mm.
The optional leakage converters are LAD-800 and LAD-1100.
Insulation resistance deterioration should be judged using effective leakage current Ior.