EnerSys PowerSafe SBS EON Technology Hybrid Applications Reserve Power Operation Guide

PowerSafe® SBS® EON Technology® solutions are well proven in stand by and cyclic applications, recent developments have focused on improving robustness in harsh environments and challenging operating conditions, so that today EON Technology now has higher cyclic performance, improved endurance at high temperature and the ability to operate in partial state of charge, providing that the operating conditions are well understood.


EnerSys PowerSafe SBS EON Technology Hybrid Applications Reserve Power Operation Guide - cover page
Brand
EnerSys
Category
VRLA Battery
Document type
User Manual
Language
English
Pages
4
File format
PDF
File size
393 KB
Published
16 November, 2023
Updated
16 November, 2023
MD5 checksum
62FDC70190092E49F88E5AD35148150E

About this manual

This guide covers general operating instructions and cyclic operation guidelines for PowerSafe SBS EON Technology monoblocs and cells used in off-grid hybrid reserve power applications. It addresses operating temperature, storage, freshening charge, commissioning, fast charging, charging current limits, disposal, and controlled full or partial state of charge operation.

The document includes charging parameters for optimized life and performance, storage time and open-circuit voltage relationships by temperature, and definitions of controlled full and partial state of charge operating modes.

What's inside

  • Applications
  • General Operating Instructions
  • Operating Temperature Range
  • Storage
  • Freshening Charge
  • Commissioning
  • Fast Charging
  • Charging Current Limit
  • Disposal
  • Cyclic Operation Guidelines

Specifications

Operating temperature range-40°C to +50°C
Shelf life at 20°C2 years
Freshening charge triggerOCV approaches 2.10 V/cell
Freshening charge voltage2.29 to 2.40 V/cell
Freshening charge duration24 hours
Commissioning charge24 hours at 2.40 V/cell, no load
Fast charge voltage2.40 V/cell at 20°C
Minimum charging currentLoad + 0.1C10 A
RecyclabilityRecyclable

Frequently asked questions

What is the recommended operating temperature range for PowerSafe SBS EON Technology monoblocs and cells in hybrid applications?

The recommended range is -40°C to +50°C, with optimum life and performance at +20°C.

When must a freshening charge be given?

A freshening charge is required when the open-circuit voltage approaches 2.10 volts per cell or maximum storage time is reached, whichever occurs first.

What commissioning charge is required before cyclic duty?

The battery must receive a 24-hour charge at a voltage equivalent to 2.40 volts per cell with no load connected.

Are PowerSafe SBS EON Technology monoblocs and cells recyclable?

Yes, they are recyclable and end-of-life batteries must be disposed of by a licensed battery recycler in compliance with local and national laws.