This manual describes the installation, operation, and maintenance of EnerSys batteries.
This manual covers receiving, storage, ventilation, installation, operation, maintenance, disposal, and shipping of EnerSys PowerSafe SBS batteries. It includes storage time and open-circuit voltage audit intervals, freshening charge instructions, float voltage ranges, and discharge voltage cut-off limits.
It also provides connector torque values, hydrogen evolution data, maintenance checks, and safety warnings for electrolyte, gases, lifting, and California Proposition 65.
| Freshening charge voltage | 2.27 Vpc |
|---|---|
| Freshening charge current limit | 10 A per 100 Ah nominal capacity |
| Freshening charge duration | At least 24 hours, maximum 48 hours |
| Acceptable float voltage range | 2.27-2.29 Vpc at 68°F (20°C); 2.25-2.27 Vpc at 77°F (25°C) |
| Minimum temperature-compensated float voltage | 2.21 Vpc |
| Storage temperature limit | Do not store below -40°F (-40°C) |
| Discharge voltage cut-off limits | 1.80 Vpc at 10 hr; 1.75 Vpc at 8 hr and 5 hr; 1.70 Vpc at 3 hr; 1.60 Vpc at 1 hr and 15 min |
| Module voltage tolerance | Within ±0.30 V of nominal float voltage |
Charge the module or string at a constant voltage equivalent to 2.27 Vpc, with current limited to 10 A per 100 Ah nominal capacity, for at least 24 hours and no more than 48 hours. The charge is complete when the current stabilizes.
Constant voltage chargers are recommended, with an acceptable float voltage range of 2.27-2.29 Vpc at 68°F (20°C) and 2.25-2.27 Vpc at 77°F (25°C). The temperature-compensated voltage should not go below 2.21 Vpc.
The battery should be stored in a clean, cool, dry area and must not be stored below -40°F (-40°C).
Measure battery string voltage, temperature, float current, inter-module resistances, and internal ohmic values; adjust float voltage if necessary; measure individual module voltages; and inspect for dust contamination and loose or corroded connections.