This manual covers receiving, storage, ventilation, installation, operation, maintenance, disposal, and shipping of EnerSys PowerSafe SBS batteries. It includes storage time and open-circuit voltage audit intervals, freshening charge instructions, float voltage ranges, and discharge voltage cut-off limits.

It also provides connector torque values, hydrogen evolution data, maintenance checks, and safety warnings for electrolyte, gases, lifting, and California Proposition 65.

What's inside

  • 1. Receiving the battery
  • 2. Storage
  • 2.1 Storage Conditions and Time
  • 2.2 Freshening Charge
  • 3. Ventilation
  • 4. Installation
  • 5. Operation
  • 6. Maintenance
  • 7. Disposal
  • 8. Shipping

Specifications

Freshening charge voltage2.27 Vpc
Freshening charge current limit10 A per 100 Ah nominal capacity
Freshening charge durationAt least 24 hours, maximum 48 hours
Acceptable float voltage range2.27-2.29 Vpc at 68°F (20°C); 2.25-2.27 Vpc at 77°F (25°C)
Minimum temperature-compensated float voltage2.21 Vpc
Storage temperature limitDo not store below -40°F (-40°C)
Discharge voltage cut-off limits1.80 Vpc at 10 hr; 1.75 Vpc at 8 hr and 5 hr; 1.70 Vpc at 3 hr; 1.60 Vpc at 1 hr and 15 min
Module voltage toleranceWithin ±0.30 V of nominal float voltage

Frequently asked questions

How should a freshening charge be performed?

Charge the module or string at a constant voltage equivalent to 2.27 Vpc, with current limited to 10 A per 100 Ah nominal capacity, for at least 24 hours and no more than 48 hours. The charge is complete when the current stabilizes.

What float voltage range is recommended?

Constant voltage chargers are recommended, with an acceptable float voltage range of 2.27-2.29 Vpc at 68°F (20°C) and 2.25-2.27 Vpc at 77°F (25°C). The temperature-compensated voltage should not go below 2.21 Vpc.

What storage temperature limit applies?

The battery should be stored in a clean, cool, dry area and must not be stored below -40°F (-40°C).

What maintenance is suggested every six months?

Measure battery string voltage, temperature, float current, inter-module resistances, and internal ohmic values; adjust float voltage if necessary; measure individual module voltages; and inspect for dust contamination and loose or corroded connections.