Featured EnerSys manuals

EnerSys PowerSafe SBS Battery Installation, Operation, and Maintenance Manual
This manual covers receiving, storage, ventilation, installation, operation, maintenance, disposal, and shipping of EnerSys PowerSafe SBS batteries. It includes storage time and open-circuit voltage audit intervals, freshening charge instructions, float voltage ranges, and discharge voltage cut-off limits.
It also provides connector torque values, hydrogen evolution data, maintenance checks, and safety warnings for electrolyte, gases, lifting, and California Proposition 65.
Covers: 1. Receiving the battery · 2. Storage · 2.1 Storage Conditions and Time · 2.2 Freshening Charge · 3. Ventilation · 4. Installation
Latest EnerSys manuals
EnerSys PowerSafe SBS Battery Installation, Operation, and Maintenance Manual
User Manual 4 pages · 800 KB · ENInstallation, operation, and maintenance manual for EnerSys PowerSafe SBS batteries, covering receiving, storage, charging, maintenance, disposal, and shipping.
Which document do I need?
User Manual
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in EnerSys manuals
How should a freshening charge be performed?
Charge the module or string at a constant voltage equivalent to 2.27 Vpc, with current limited to 10 A per 100 Ah nominal capacity, for at least 24 hours and no more than 48 hours. The charge is complete when the current stabilizes.
From: EnerSys PowerSafe SBS Battery Installation, Operation, and Maintenance Manual
What float voltage range is recommended?
Constant voltage chargers are recommended, with an acceptable float voltage range of 2.27-2.29 Vpc at 68°F (20°C) and 2.25-2.27 Vpc at 77°F (25°C). The temperature-compensated voltage should not go below 2.21 Vpc.
From: EnerSys PowerSafe SBS Battery Installation, Operation, and Maintenance Manual