NDZ3 DC contactor adopts modular design, with the characteristics of small size, light weight, easy installation and long service life.
The NDZ3 series DC contactors are designed for DC circuits up to 1000V with rated currents from 50A to 250A. They feature IP67 protection, meet GB 14048.4, GB 14048.5, IEC 60947-4-1, and IEC 60947-5-1 standards, and carry CCC, CB, CE, and TUV certifications. The contactors operate in temperatures from -40°C to +85°C and humidity 5%-95%.
Key features include a compact design with high short-time withstand current (15Ie/30ms), low contact resistance (100A 50mV), and multiple coil voltage options (DC12V, DC24V, DC48V, DC12-36V). Auxiliary contacts are available as 1NO, 1NC, or 1NO+1NC. The document provides technical parameters, electrical life curves, current-time curves, outline and installation dimensions, wiring diagrams, and installation precautions including torque requirements for terminal screws. This manual is written in Chinese.
| Rated Insulation Voltage (Ui) | DC1000V |
|---|---|
| Conventional Free Air Thermal Current (Ith) | 150A (NDZ3-50/100), 300A (NDZ3-150), 500A (NDZ3-200/250) |
| Rated Operational Current (Ie) at DC-450V/500V | 50A, 100A, 150A, 200A, 250A |
| Short-time Withstand Current | 750A 30ms (50A), 1500A 30ms (100A), 2250A 30ms (150A), 3000A 30ms (200A), 3750A 30ms (250A) |
| Contact Resistance | 100A 50mV |
| Insulation Resistance | 100MΩ at 500VDC |
| Power Frequency Withstand Voltage | 2500VAC 60s (50-150A), 3500VAC 60s (200-250A) |
| Mechanical Life | 100×10^4 operations, 1200 operations/h |
| Electrical Life (DC 500V L/R≤1ms) | 6000 operations at rated current |
| Auxiliary Contact Configuration | 1NO, 1NC, 1NO+1NC |
| Auxiliary Contact Rating | 2A 30VDC / 3A 125VAC |
| Coil Voltage (Us) | DC12V, DC24V, DC48V, DC12-36V |
| Coil Operating Voltage Range | 75%-110% Us (50-150A), 75%-100% Us (200-250A) |
| Coil Release Voltage Range | 10%-60% Us |
| Closing Time | ≤35ms |
| Opening Time | ≤15ms |
| Coil Inrush Current | 0.5A (50-150A), 3.5A (200-250A) |
| Shock Resistance (Half-sine) | 11ms 15g (50-150A), 11ms 30g (200-250A) |
| Vibration Resistance | 10g 10-500Hz (50-150A), 20g 10-1000Hz (200-250A) |
| Protection Degree | IP67 |
| Pollution Degree | III |
| Installation Category | III |
| Mounting Orientation | Vertical or horizontal |
| Terminal Screw Torque (M8) | 7-8 N·m |
| Terminal Screw Torque (M6) | 4-5 N·m |
| Terminal Screw Torque (M5) | 3.5-4.5 N·m |
| Minimum Conductor Cross-section | 10mm² (50A), 35mm² (100A), 50mm² (150A), 95mm² (200A), 120mm² (250A) |
The rated insulation voltage (Ui) is DC1000V.
Available coil voltages are DC12V, DC24V, DC48V, and DC12-36V depending on model.
The contactors have IP67 protection degree.
The series complies with GB 14048.4, GB 14048.5, IEC 60947-4-1, and IEC 60947-5-1.