Changshu Switch CK3-105 to CK3-800 Magnetic Contactor Instruction Manual

Bilingual instruction manual for Changshu Switch CK3-105 to CK3-800 magnetic contactors, covering mounting, wiring, maintenance, SCPD and RoHS.


Changshu Switch CK3-105 to CK3-800 Magnetic Contactor Instruction Manual - cover page
Brand
常熟开关
Category
Contactors
Document type
User Manual
Language
Chinese
Pages
2
File format
PDF
File size
781 KB
Published
09 November, 2026
Updated
09 November, 2026
MD5 checksum
140C0748A07F464B875AFD1D8A143A1D

About this manual

This bilingual Chinese/English instruction manual covers the CK3-105, CK3-125, CK3-150, CK3-180, CK3-220, CK3-300, CK3-400, CK3-600 and CK3-800 magnetic contactors, including the J variants marked with *1. It starts with safety precautions ranked as "Warning" and "Caution", then walks through unpacking and checking the type, coil voltage and contact arrangement, storage in the original packing box, and mounting on a dry, clean and stable surface with an inclination of no more than 30°.

Further sections give the mounting space from Table 1, connection of the main terminals (wire size and tightening torque in Table 2), how the operation indicator shows contactor status, and maintenance and inspection — checks before operation, periodic inspection, and removal and installation of the arc chamber for the 105 to 400 and the 600/800 types. Short circuit protective device selection (Type 1 and Type 2) and the RoHS directive statement with the hazardous substances table close the document. This manual is written in Chinese.

What's inside

  • Safety Precautions
  • Unpacking
  • Storage
  • Mounting
  • Mounting space
  • Connection
  • Usage
  • Maintenance and inspection
  • Short circuit protective device (SCPD)
  • RoHS Directive

Specifications

Contactor types coveredCK3-105, CK3-125, CK3-150, CK3-180, CK3-220, CK3-300, CK3-400, CK3-600, CK3-800 (including J variants)
Holding power, CK3-105, 125, 150, 125J, 150J10.0 VA
Holding power, CK3-180, 220, 300, 400, 180J, 220J13.0 VA
Holding power, CK3-105J20.0 VA
Holding power, CK3-60015.0 VA
Allowable coil voltage fluctuation range80 to 110% of coil voltage (85 to 110% for CK3-105J)
Permissible mounting inclination30° or less
Recommended spacing for close mounting20 mm or more between units
Coil voltage with DC single-phase full-wave rectification100 to 110V for the 100V type, 200 to 220V for the 200V type
Main terminalsEach terminal can connect 2 crimp terminals

Frequently asked questions

What is the allowable voltage fluctuation range of the coil voltage?

It is 80 to 110% of the coil voltage; for the CK3-105J it is 85 to 110%.

At what angle can the contactor be mounted?

It is mounted on a vertical surface and must not incline more than 30°.

What spacing is recommended when units are installed very closely?

Installing the units 20 mm or more apart is recommended, because close mounting may raise the temperature and shorten coil life.

Should dark or rough contacts be refinished or greased?

No. Dark and rough contacts can still function, so they should not be refinished or greased; replace the product if the contact facings are badly eroded and the carrier material is visible.

Download PDF (781 KB)