This manual describes the installation instructions for the air conditioner outdoor unit.
This document is an installation manual for the outdoor unit of an air conditioner that uses R410A refrigerant. The main body is written in traditional Chinese, while the multilingual cover also carries the title in other languages such as Vietnamese (HƯỚNG DẪN LẮP ĐẶT) and Indonesian (PANDUAN PEMASANGAN, UNIT LUAR), and it is intended for authorized service personnel. The document carries part number 9377863294.
The manual explains that it only covers installation of the outdoor unit and refers readers to the indoor unit's own installation manual. It covers safety precautions, notes that the unit is not explosion-proof and must be installed by authorized personnel, and explains R410A-specific requirements such as dedicated tools, minimum copper pipe wall thickness, refrigerant piping length limits, additional refrigerant charge, pipe diameters, and electrical wiring with a dedicated circuit breaker and earth leakage breaker. This manual is written in Chinese.
| Refrigerant | R410A |
|---|---|
| Rated voltage | 230 V (50 Hz) |
| Operating voltage | 198-264 V |
| Minimum copper pipe wall thickness | 0.8 mm |
| Max piping length / height difference (24 type) | 30 m / 20 m |
| Max piping length / height difference (12, 18 type) | 25 m / 15 m |
| Additional refrigerant charge | 20 g per meter beyond 15 m |
| Earth leakage breaker | 30 mA, 0.1 s or less |
It uses the new R410A refrigerant, and dedicated R410A tools, piping and flare nuts must be used instead of parts made for R22.
No. Reusing R22 piping and flare nuts would raise the pressure inside the refrigerant circuit and cause damage or injury, so R410A-dedicated materials must be used.
The unit is pre-charged for 15 m of piping; beyond that, additional refrigerant is charged at a standard of 20 g per meter according to the table.
Wait at least 10 minutes after the power is off before touching electrical parts, otherwise an electric shock may occur.