Condensate drain MK 35 for draining condensate or as a steam vent from water vapour.
The GESTRA MK 35/31 and MK 35/32 are thermal condensate drain steam traps for discharging condensed water from steam lines or for air venting. The document states that only qualified staff may install them and that work must be done with the system depressurized and cold.
The installation guide also describes membrane options, installation position, flow direction, required service clearance, welding limits, and technical data for the traps. This manual is written in German.
| Product type | Thermal condensate drain |
|---|---|
| Intended use | Discharge of condensed water from steam lines or air venting |
| CE marking | No |
| PED category | Exception pursuant to article 3.3 |
| Installation position | Any position |
| Housing seal | Asbestos-free graphite/CrNi |
| Normal membrane closing | 10 K before steam temperature |
| Subcooled membrane closing | 30 K before steam temperature |
| MK 35/31 closure | Tandem closure, double seal |
| MK 35/32 closure | Flat seat |
| Service clearance | At least 30 mm |
| Welding process | Arc fusion welding, processes 111 and 141 per DIN EN 24063 |
Use it only for discharging condensed water from steam lines or for air venting.
Installation must be performed only by qualified staff.
Only when the system is depressurized and cold.
Only arc fusion welding, processes 111 and 141 per DIN EN 24063.