GESTRA MK 35/31 and MK 35/32 Condensate Drain Steam Trap Installation Instructions

Condensate drain MK 35 for draining condensate or as a steam vent from water vapour.


GESTRA MK 35/31 and MK 35/32 Condensate Drain Steam Trap Installation Instructions - cover page
Brand
GESTRA
Category
Other products
Document type
Installation Guide
Language
German
Pages
33
File format
PDF
File size
177 KB
Published
11 November, 2023
Updated
11 November, 2023
MD5 checksum
1A4FA5CCECF65CBBDEE4E90782FAB721

About this manual

The GESTRA MK 35/31 and MK 35/32 are thermal condensate drain steam traps for discharging condensed water from steam lines or for air venting. The document states that only qualified staff may install them and that work must be done with the system depressurized and cold.

The installation guide also describes membrane options, installation position, flow direction, required service clearance, welding limits, and technical data for the traps. This manual is written in German.

What's inside

  • Sicherheitshinweis
  • Bestimmungsgemäßer Gebrauch
  • Danger
  • Ratings pursuant to article 9 of the PED
  • Systembeschreibung
  • Einbau
  • Technical Data

Specifications

Product typeThermal condensate drain
Intended useDischarge of condensed water from steam lines or air venting
CE markingNo
PED categoryException pursuant to article 3.3
Installation positionAny position
Housing sealAsbestos-free graphite/CrNi
Normal membrane closing10 K before steam temperature
Subcooled membrane closing30 K before steam temperature
MK 35/31 closureTandem closure, double seal
MK 35/32 closureFlat seat
Service clearanceAt least 30 mm
Welding processArc fusion welding, processes 111 and 141 per DIN EN 24063

Frequently asked questions

What is the intended use of the GESTRA MK 35 steam trap?

Use it only for discharging condensed water from steam lines or for air venting.

Who is allowed to install the GESTRA MK 35/31 and MK 35/32?

Installation must be performed only by qualified staff.

When can installation or maintenance work be carried out?

Only when the system is depressurized and cold.

Which welding process is permitted for the weld socket?

Only arc fusion welding, processes 111 and 141 per DIN EN 24063.