Technical data and specifications for the GESTRA NRGS 15-1 compact level monitoring system used in steam boilers and hot-water installations.
The GESTRA NRGS 15-1 is a compact-type system designed for water level monitoring and limiting in steam boilers, pressurized hot-water installations, and condensate or feedwater collecting tanks. It consists of a level electrode with four tips and an integrated level switching controller.
The device operates with water having a minimum electrical conductivity of > 0.5 μS/cm at 25 °C. It features time-delayed switching channels, output relays, and signal LEDs. The system includes a ten-pole code switch to select sensitivity ranges and establish specific functions, such as low/high level alarms and timed pump control.
| Service pressure | PN 25, 25 bar at 224 °C |
|---|---|
| Mechanical connection | Screwed G 1A, ISO 228 |
| Materials (Screw-in body) | 1.4571, CrNiMoTi17-12-2 or 1.4404, A 470 316L |
| Electrode rods Length supplied | 1000 mm |
| Electrode rods Diameter | 5 mm |
| Supply voltage | 220 – 240 V +10/–15 %, 50/60 Hz |
| Power consumption | 3 VA |
| Response sensitivity | > 0.5 ... < 1000 μS/cm or > 10 ... < 10000 μS/cm |
| Output | 4 volt-free change-over contacts, 8 A 250 V AC / 30 V DC |
| Protection | IP 65 to DIN EN 60529 |
| Ambient temperature (operation) | 0 ° ... 70 °C |
The device works with water having a minimum electrical conductivity of > 0.5 μS/cm at 25 °C.
Yes, the response sensitivity is switch-selectable between > 0.5 ... < 1000 μS/cm and > 10 ... < 10000 μS/cm.
No, according to the European Directive 2014/34/EU, the equipment must not be used in potentially explosive areas.