The MCWL Series laser water chiller is industrial cooling equipment designed for machine tools, drive motors, and electric spindles, providing a stable and precise cooling medium. Its refrigeration system uses a compressor, condenser, evaporator, and throttling device to transfer heat from the cooled medium.

The manual covers safety warnings, operating conditions, model designation, installation and commissioning, maintenance, troubleshooting, transportation, storage, disposal, and other service information. This manual is written in Chinese.

What's inside

  • Warnings
  • Overview
  • Operating conditions
  • Model description
  • Installation and commissioning
  • Maintenance
  • Troubleshooting
  • Transportation requirements
  • Storage requirements
  • Disposal

Specifications

Ambient temperature5 to 45 C
Ambient humidity<=90% RH
Altitude<=3000 m
Allowed cooling mediumSoftened water (pure, distilled, high-purity water)
Allowed antifreeze content<=30% ethylene glycol or <=20% ethanol by volume
Prohibited mediaAutomotive antifreeze, water-tank additive, >30% antifreeze, and other listed media
Pipe pressure drop<=0.5 bar
Pipe pressure ratingAt least 1.5 times pump supply pressure

Frequently asked questions

What cooling media are allowed for the chiller?

Softened water such as pure, distilled, or high-purity water is allowed, along with up to 30% ethylene glycol or 20% ethanol by volume and manufacturer-approved corrosion inhibitors or algicides.

What media must not be used?

Automotive antifreeze, water-tank additive, more than 30% antifreeze, flammable liquids such as acetone, oils, pharmaceutical or food liquids, and other listed corrosive or particle-containing liquids must not be used.

What ambient temperature range is allowed?

The allowed ambient temperature range is 5 to 45 C.

How does the winter freeze-protection logic work?

When the chiller is powered on standby and the ambient temperature is below 10 C, the circulation pump starts when the freeze water temperature is below 5 C and the water-tank heater starts below 3 C; they stop when the freeze water temperature exceeds 10 C, and the logic exits when the ambient temperature reaches 11 C.