This document describes the installation instructions and user guide for the White-Rodgers™ thermostat.
The White-Rodgers BP150, BP150C, BP125C and 1E65-151 are line voltage programmable thermostats for electric heating units such as electric baseboards, convectors and aeroconvectors. They are designed for resistive loads from 1.25 A to 12.5 A at 120/240 VAC and are not compatible with central heating systems.
The document explains where to mount the thermostat, how to connect two- or four-wire installations, and how to use Manual, Automatic and Preprogrammed modes. It also covers clock and day adjustment, Celsius/Fahrenheit display, set point limits and technical specifications.
| Supply voltage | 120/208/240 VAC, 50/60 Hz |
|---|---|
| Minimum electrical current with a resistive load | 1.25 A (150 W @ 120 V; 260 W @ 208 V; 300 W @ 240 V) |
| Maximum electrical current with a resistive load | 12.5 A (1500 W @ 120 V; 2600 W @ 208 V; 3000 W @ 240 V) |
| Temperature display range | 3°C to 40°C (37°F to 99.5°F) |
| Temperature display resolution | 0.5°C (0.5°F) |
| Temperature set point range | 3°C to 30°C (37°F to 86°F) |
| Temperature set point increments | 0.5°C (1°F) |
| Storage temperature | -40°C to 50°C (-104°F to 122°F) |
It supports a resistive load from 1.25 A to 12.5 A at 120/240 VAC.
It should be mounted to a connection box on a wall facing the heating unit, about 1.5 m (5 feet) above the floor.
The modes are Manual, Automatic and Preprogrammed.
The set point range is 3°C to 30°C (37°F to 86°F).