This document describes Nuaire's constant pressure system, which uses branched ductwork connected to a Nuaire constant pressure fan. For each inlet to the system, there will be a surface mounted model NRG dual volume flow rate grille.
This user guide (leaflet number 671238) from Nuaire, a trading division of Polypipe Limited, explains how to commission constant pressure ventilation systems that use 12/230V surface mounted grilles. The system is an arrangement of branched ductwork connected to a Nuaire constant pressure fan, with a surface mounted NRG dual volume flow rate grille at each inlet. The fan has an integral speed control and pressure sensor and automatically adjusts its speed to maintain a target pressure.
The NRG grille carries a Passive Infra-Red (PIR) occupancy sensor that opens the damper when movement is detected, and the damper returns to its closed position about ten minutes after the last occupant. The guide lists the information required before commissioning and walks through balancing the ductwork, setting the boost ventilation rate with the face mounted slider switch, adjusting the Set Target Pressure potentiometer at the fan control box, and checking damper operation and flow rates. It is an addendum to I&M documents 671153, 671154, 671172, 671170 and 671171.
| Maximum inlet system static pressure | 100 Pa |
|---|---|
| Damper static pressure | Twice the inlet pressure |
| Damper auto-close delay | Approximately 10 minutes after last occupant detected |
| Fan speed response/settling time | Up to 30 seconds |
| Grille power supply | 12/230V transformer |
| Boost flow rate adjustment | Slider switch at front of unit; trickle rate pre-set |
The boost (open) flow rate is set with a slider switch at the front of the unit. The trickle (closed) flow rate is pre-set and not adjustable.
Measure the static pressure at the ducting just before the fan casing and adjust the Set Target Pressure potentiometer at the fan control box until the specified static pressure is achieved. The fan speed change response may take up to 30 seconds.
Add together the inlet system pressure and the damper static pressure.
The integral Passive Infra-Red (PIR) sensor opens the damper when it senses movement, and the damper closes again about ten minutes after the last occupant is detected.