FLS M9.50 Batch Controller User Manual

The FLS M9.50 Batch Controller is a dedicated electronic device for accurate control of batching or mixing of different liquids.


FLS M9.50 Batch Controller User Manual - cover page
Brand
FLS
Category
Automation control Equipment
Document type
User Manual
Language
Chinese
Pages
16
File format
PDF
File size
1.6 MB
Published
08 November, 2023
Updated
08 November, 2023
MD5 checksum
DA98F38A738BDF9432A4846CB5D471EA

About this manual

The FLS M9.50 is a dedicated electronic batch controller for accurately controlling the batching or mixing of different liquids. It has a 4-inch wide-screen full graphic display with a three-color backlight, and it can store up to 10 batches with 10 different calibration k coefficients.

The manual covers safety notes and the packing list, technical data, panel and wall mounting, terminal wiring and relay/SSR connections, batch programming and settings, source solution volume alarms, and software updates through the USB port. It also lists ordering data and accessories. This manual is written in Chinese.

What's inside

  • Safety instructions and packing list
  • Technical data
  • Mechanical installation
  • Wiring
  • USB port and software update
  • Batch programming
  • Settings menu
  • Digital outputs
  • Source solution volume alarm
  • Ordering data

Specifications

Power supply12 - 24 VDC ±10% (regulated)
Maximum current consumption300 mA
DisplayLC full graphic display
Backlight3 colors
Flow input range (frequency)0 to 1500 Hz
Flow input accuracy (frequency)0.5%
Operating temperature-20°C to +70°C (-4°F to 158°F)
Storage temperature-30°C to +80°C (-22°F to 176°F)
Enclosure protectionFront IP65
Solid state relay outputs2 x, optically isolated; 50 mA max leakage current; 24 VDC max pull-up voltage
Relay outputsMechanical SPDT contacts
Batch storage10 batches with 10 different calibration k coefficients
Terminal wire size26 to 12 AWG (0.08 to 2.5 mm2)

Frequently asked questions

What power supply does the FLS M9.50 require?

The controller requires a regulated 12 to 24 VDC supply with ±10% tolerance.

How many batches can the M9.50 store?

It can store 10 batches, each with its own calibration k coefficient.

What is the front enclosure protection rating?

The front of the enclosure has an IP65 protection rating.

How is the M9.50 software updated?

Software is updated through the USB port using a USB cable, the FLS calibration system software and the new update software downloaded from the FLS website.

Download PDF (1.6 MB)