NHR-D4 Series Intelligent Power Transducer User Manual

The NHR-D4 series intelligent power transducer adopts fully isolated technology, and can directly collect AC voltage and current signals. It can measure power frequency, voltage, current, phase difference, and single-phase and three-phase balanced power. It adopts a dedicated integrated chip with strong anti-interference ability and high stability. Through the programmer, the display range and transmitter output range can be modified online. With LCD display function, RS485 communication function, using standard MODBUS RTU protocol to connect with上位机can构成数据采集系统及控制系统.


NHR-D4 Series Intelligent Power Transducer User Manual - cover page
Brand
NHR
Category
sensor
Document type
User Manual
Language
Chinese
Pages
4
File format
PDF
File size
308 KB
Published
07 November, 2023
Updated
07 November, 2023
MD5 checksum
6EFD9AFBF953929FE91946FB0B4651CE

About this manual

The NHR-D4 Series intelligent power transducer uses full isolation to collect AC voltage and current signals. It measures power frequency, voltage, current, phase difference, and single-phase or three-phase balanced power, and it has a liquid-crystal display and RS485 communication using standard MODBUS RTU protocol.

The manual covers the display panel appearance, model selection, technical specifications, wiring diagrams, power calculation formulas, and parameter settings. It also notes that the communication function and transmitter output function can only be selected one at a time. This manual is written in Chinese.

What's inside

  • Product introduction
  • Display panel appearance
  • Model selection table
  • Technical specifications
  • Wiring diagram
  • Power calculation formulas
  • Parameter settings

Specifications

AC voltage input100V/250/300V/400V/500V
AC current input0.5A/1A/2A/3A/4A/5A
Output signals4-20mA, 0-10mA, 0-20mA, 1-5V, 0-5V
Output loadCurrent output ≤500Ω; voltage output ≥250KΩ
CommunicationMODBUS-RTU; RS485 ≤1000 m; RS232 ≤10 m; ≤9.6 kbps
Power supplyDC24V (±10%), AC100-240V, 50/60Hz
Insulation impedance≥100MΩ at 500VDC
Dielectric strength1500Vrms for 1 min, no spark
Operating temperature0 to 50°C, no condensation or ice
Installation35mm DIN rail mounting
Dimensions22.5 x 110 x 115 mm (W x H x D)
Transmission accuracy0.3%FS
Response time≤1S

Frequently asked questions

What communication protocol does the NHR-D4 use?

It uses the MODBUS-RTU protocol for communication.

What is the maximum RS485 transmission distance?

The RS485 transmission distance is ≤1000 meters.

Can the NHR-D4 have both communication and transmitter output?

No. The communication function and transmitter output function can only be selected one at a time.

How are current and voltage outputs switched?

Current and voltage outputs are switched through J2 on the main board.

Download PDF (308 KB)