Installation instructions for contractors covering the flue gas system for Vitocrossal (type CU3), Vitodens, and Vitoladens boilers, including safety…
This document provides installation instructions for contractors regarding the flue gas system compatible with Vitocrossal (type CU3), Vitodens, and Vitoladens boilers. It outlines safety protocols, general installation guidelines, and specific requirements for routing flues through ducts or as technical units. The guide emphasizes the need for competent personnel to perform installation, initial start-up, inspection, maintenance, and repairs.
The flues are approved for use with flue gas temperatures up to 120°C.
Air must be pumped into the sealed flue until a pressure of 200 Pa has built.
The flue pipe is deemed sound if the CO2 concentration is no higher than 0.2%.