This document describes the installation, operation and maintenance of the SG36_60CX-US PV grid-connected inverter.
This user manual is for the Sungrow SG36CX-US and SG60CX-US PV grid-connected inverters. It describes product information and guidelines for installation, operation, and maintenance, and states that it is intended for qualified personnel responsible for installation and commissioning and for inverter owners who interact with the inverter.
The manual covers safety, product introduction, unpacking and storage, mechanical mounting, electrical connection, commissioning, the iSolarCloud App, system decommissioning, troubleshooting and maintenance, and technical data. It also includes AC and DC cable connection, RS485 communication, dry contact connection, and optional communication module and module-level rapid shutdown device connection.
| Inverter models covered | SG36CX-US, SG60CX-US |
|---|---|
| Maximum parallel inverters connected to the grid | 30 |
| Internal capacitor discharge wait time | At least 5 minutes |
| Recommended transformer short-circuit impedance | 6% (permissible tolerance: ±10%) |
| Maximum system cable voltage drop | 3% |
The manual is valid for the SG36CX-US and SG60CX-US inverter types.
Wait at least 5 minutes for the internal capacitors to discharge, and ensure there is no voltage or current before pulling any connector.
The total number of parallel inverters must not exceed 30; contact SUNGROW for technical approval above that.
No. Do not open the enclosure at any time; unauthorized opening voids guarantee and warranty claims.