Sungrow SG36_60CX-US (SG36CX-US/SG60CX-US) PV Grid-Connected Inverter User Manual

This document describes the installation, operation and maintenance of the SG36_60CX-US PV grid-connected inverter.


Sungrow SG36_60CX-US (SG36CX-US/SG60CX-US) PV Grid-Connected Inverter User Manual - cover page
Brand
Sungrow
Category
inverter
Document type
User Manual
Language
English
Pages
107
File format
PDF
File size
19.4 MB
Published
07 November, 2023
Updated
07 November, 2023
MD5 checksum
F3FCF18D43501998AD9B602355C3FF9C

About this manual

This user manual is for the Sungrow SG36CX-US and SG60CX-US PV grid-connected inverters. It describes product information and guidelines for installation, operation, and maintenance, and states that it is intended for qualified personnel responsible for installation and commissioning and for inverter owners who interact with the inverter.

The manual covers safety, product introduction, unpacking and storage, mechanical mounting, electrical connection, commissioning, the iSolarCloud App, system decommissioning, troubleshooting and maintenance, and technical data. It also includes AC and DC cable connection, RS485 communication, dry contact connection, and optional communication module and module-level rapid shutdown device connection.

What's inside

  • Safety
  • Product Introduction
  • Unpacking and Storage
  • Mechanical Mounting
  • Electrical Connection
  • Commissioning
  • iSolarCloud App
  • System Decommissioning
  • Troubleshooting and Maintenance
  • Technical Data

Specifications

Inverter models coveredSG36CX-US, SG60CX-US
Maximum parallel inverters connected to the grid30
Internal capacitor discharge wait timeAt least 5 minutes
Recommended transformer short-circuit impedance6% (permissible tolerance: ±10%)
Maximum system cable voltage drop3%

Frequently asked questions

Which inverter models are covered by this manual?

The manual is valid for the SG36CX-US and SG60CX-US inverter types.

What should be done before pulling any connector?

Wait at least 5 minutes for the internal capacitors to discharge, and ensure there is no voltage or current before pulling any connector.

How many inverters can be connected in parallel to the grid?

The total number of parallel inverters must not exceed 30; contact SUNGROW for technical approval above that.

Can the inverter enclosure be opened?

No. Do not open the enclosure at any time; unauthorized opening voids guarantee and warranty claims.