About this manual

This leaflet describes the Pietro Fiorentini HBC 975, a compact slam shut valve (SAV) with self-operated actuation and manual resetting. The device intercepts gas flow when the monitored pressure reaches preset limits, or when it is tripped manually at the installation point or by an optional remote command. It is intended for transmission networks, large industrial installations and other high profile applications, and is suitable for natural gas and all non-corrosive gaseous media.

The document lists the main features, including overpressure and/or underpressure intervention, a manual push-button control, an optional 3-way solenoid valve for remote control, manual re-setting and an internal by-pass for pressure equalization before resetting. It also gives body and seal materials, design pressure and temperature ranges, intervention ranges, accuracy class, available sizes and flanging, KG flow coefficients, pressure switch set point ranges, installation notes on filtering and the sensing line, and overall dimensions and weights.

What's inside

  • General Information
  • Main Features
  • Materials
  • Design pressure and temperature
  • Range of intervention for overpressure and underpressure
  • Available sizes and flanging
  • KG valve coefficient
  • Pressure switches (OPSO / UPSO set point ranges)
  • Installation
  • Dimensions and Weights

Specifications

Design pressure PS51.7 bar (749.6 psi) for class 300; 102 bar (1479 psi) for class 600
Design temperature-20 °C to +60 °C (-4 °F to +140 °F)
Ambient temperature-20 °C to +60 °C (-4 °F to +140 °F)
Range of intervention for overpressure (Who)1.0 to 85 bar (145 to 1232 psi)
Range of intervention for underpressure (Whu)0.4 to 75 bar (58 to 1087 psi)
Accuracy class AGup to 1 (depending on setting pressure)
Available sizesDN 4" - 6" - 8" - 10"
Flangingclass ANSI 300 - ANSI 600 RF or RTJ according to ANSI16.5
Body materialCast steel ASTM A352 LCC for class 300 and 600
Valve seat and plug materialSteel + vulcanized rubber
SealsNitril rubber
Compression fittingAccording to DIN 2353 in zinc-plated carbon steel
KG flow coefficient, 4" (DN 100)8416
KG flow coefficient, 10" (DN 250)38425

Frequently asked questions

What gases is the HBC 975 suitable for?

It is suitable for natural gas and all non-corrosive gaseous media.

How is the HBC 975 reset after tripping?

It is reset manually; an internal by-pass equalizes pressure before resetting.

What is the advantage of the top entry design?

It allows easy maintenance without removing the body from the pipeline.

What should be observed when installing the HBC 975?

The gas must be adequately filtered, and the sensing line nipple must be correctly positioned with the stated straight pipe lengths upstream and downstream of the take-off.