Pietro Fiorentini HBC 975 Slam Shut Valves Product Leaflet

HBC 975 is a slam-shut valve with self operated actuation and manual resetting. It is an ideal product for transmission networks, large industrial and any high profile application. HBC 975 is suitable for natural gas and all non-corrosive gaseous media.


Pietro Fiorentini HBC 975 Slam Shut Valves Product Leaflet - cover page
Brand
PIETRO FIORENTINI
Document type
Product Leaflet
Language
English
Pages
8
File format
PDF
File size
467 KB
Published
23 August, 2022
Updated
28 September, 2023
MD5 checksum
B860F5B49A8583E5271EB499BB4A1E88

About this manual

The Pietro Fiorentini HBC 975 is a compact safety valve (SAV) designed to quickly intercept gas flow when pressure reaches pre-set limits or via manual/remote command. It features a 'top entry' design that allows for easy maintenance without removing the body from the pipeline, making it suitable for transmission networks and high-profile industrial applications.

What's inside

  • General Information
  • Main Features
  • Materials
  • Pressure Switch Set point range
  • Installation Requirements
  • Dimensions

Specifications

Design pressure PS (Class 300)51,7 bar (749,6 psi)
Design pressure PS (Class 600)102 bar (1479 psi)
Design temperature-20 °C to +60 °C (-4 °F to + 140 °F)
Ambient temperature-20 °C to +60 °C (-4 °F to + 140 °F)
Available sizeDN 4” - 6” - 8” - 10"
Accuracy class AGup to 1 (depending on setting pressure)

Frequently asked questions

What media is the HBC 975 suitable for?

It is suitable for natural gas and all non-corrosive gaseous media.

How does the HBC 975 allow for maintenance?

It features a 'top entry' design that allows easy maintenance without removing the body from the pipeline.

What are the intervention ranges for overpressure?

The range of intervention for overpressure is 1,0 to 85 bar (145 to 1232 psi).