The Computer SMART III 6 FAST 12Vdc / SMART III 12 FAST 12Vdc regulator measures the power grid cosine and controls capacitor connection and disconnection in order to correct it. It also calculates and displays the main electrical parameters of balanced or unbalanced single-phase and three-phase networks.
This is a Spanish/English programming and commissioning guide for the Circutor Computer SMART III 6 FAST 12Vdc and SMART III 12 FAST 12Vdc reactive energy regulators. The text states that these regulators measure the power grid cosine and control capacitor connection and disconnection to correct it, and that they calculate and display main electrical parameters in balanced or unbalanced single-phase and three-phase networks.
The guide covers keyboard functions and display indicators, a C/K factor table and calculation example, and configuration screens for password, current transformer ratio, target cos phi, connection and reconnection times, connection type, phase sequence, number of stages, stage program and C/K factor. It also refers to an advanced setup and shows a simulation display for connecting previously indicated steps, with the full manual available from the Circutor website.
| Number of relay outputs | 6, 12 or 14 depending on model |
|---|---|
| CT primary range | 1 to 9999 |
| CT secondary values | 1 or 5 |
| Connection types | 3U3C, 3U1C, 2U1C |
| Recommended t.on / t.rec | 10 / 50 |
| Network types | Balanced or unbalanced single-phase and three-phase |
| Displayed parameters | Main electrical parameters |
It measures the power grid cosine and controls capacitor connection and disconnection to correct it.
The guide states 6, 12 or 14 outputs according to model.
The recommended values are t.on = 10 and t.rec = 50.
The possible secondary values are 1 or 5.