Circutor CVM-NET Three-Phase Industrial Network Analyzer Modbus Configuration Manual

CVM-NET is a three-phase industrial network analyzer produced by CIRCUTOR. It has a variety of measurement functions, and the measurement results can be displayed in the table.


Circutor CVM-NET Three-Phase Industrial Network Analyzer Modbus Configuration Manual - cover page
Brand
Circutor
Category
Network Analyzer
Document type
User Manual
Language
Spanish
Pages
2
File format
PDF
File size
1.8 MB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
D59BFB8168D08CE4E6B76E5DC49FC266

About this manual

The CVM-NET from CIRCUTOR is an instrument that measures and calculates the main electrical parameters in three-phase industrial networks, balanced or unbalanced. Measurement is performed in true RMS using three AC voltage inputs and three AC current inputs via current transformers with an In/5 A ratio.

This Spanish-language manual explains the device's single RESET key, and how to configure the unit, which has no keyboard, through Modbus/RTU commands or CIRCUTOR's PowerStudio software. It covers communication parameters, voltage and current transformer ratios, maximum demand calculation, clearing of maxima/minima, and the configuration and use of the two digital outputs as alarms or energy pulse outputs. This manual is written in Spanish.

What's inside

  • Keyboard (RESET key)
  • Configuration
  • Communication parameters configuration
  • Transformer ratio configuration
  • Maximum demand configuration
  • Clearing maxima and minima
  • Digital outputs configuration and use

Specifications

Measurement inputs3 AC voltage inputs and 3 AC current inputs (via In/5 A current transformers)
Default communication parametersPeripheral 3, 19200/8/N/1
Digital outputs2, remotely controllable or usable as alarms / energy pulses
Maximum demand integration time0 to 60 minutes (sliding window method)
Voltage transformer ratio rangePrimary 0 to 100,000; secondary 0 to 999
Current transformer ratio rangePrimary 0 to 10,000

Frequently asked questions

How do I perform a functional reset of the CVM-NET?

Press the RESET key for at least one second and the device will initialize its system within 5 seconds.

What are the factory default communication parameters of the CVM-NET?

The device defaults to peripheral number 3 with 19200 baud, 8 data bits, no parity and 1 stop bit (19200/8/N/1).

How can the CVM-NET be configured if it has no keyboard?

Configuration parameters must be sent to the device via Modbus/RTU commands or through CIRCUTOR's PowerStudio software, which can be downloaded free from www.circutor.es.

How do I restore the default communication parameters?

Remove the auxiliary power supply, press and hold the RESET key while re-powering the device; 5 seconds after initialization it restores the factory configuration.

Download PDF (1.8 MB)