Godgoal DCM631 Series Power Automatic Switching Device (PASD) User Manual

DCM631 Series Power Automatic Switching Device( PASD) User Manual, introduces the product model, application scope, features, function configuration, hardware configuration, technical parameters, assembly, terminal introduction, typical wiring diagram, construction precautions, operation guide, PASD software logic, parameter setting, debugging methods and precautions, and product selection.


Godgoal DCM631 Series Power Automatic Switching Device (PASD) User Manual - cover page
Brand
GODGOAL
Category
Automation control Equipment
Document type
User Manual
Language
Chinese
Pages
53
File format
PDF
File size
1.6 MB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
65342129F63E9973B6B0EBEB92BD1085

About this manual

This is the user manual for the Godgoal DCM631 Series low-voltage power automatic switching device (PASD), issued by Nanjing Godgoal Electric Automation Co., Ltd. The device is used in low-voltage distribution systems below 690V to switch quickly and reliably between main and backup power supplies, and it embeds a PLC module with selectable logic functions and adjustable time parameters. It combines three-phase measurement and display, digital inputs and outputs, and network communication, connecting to monitoring systems through a standard RS-485 interface.

The manual covers the product overview, the model range and applications (DCM-631B, Z, K, M, Q, F, T, G and S), main features, function and hardware configuration tables, technical parameters, installation and terminal descriptions, a wiring diagram for each model, construction notes, the operating guide, the switching software logic of each model, parameter setting, commissioning methods and product selection. A short English section repeats the overview, features, hardware, connection ports, wiring diagram and panel information. This manual is written in Chinese.

What's inside

  • Overview
  • Model and Application Scope
  • Main Features
  • Function Configuration Table
  • Hardware Configuration
  • Technical Parameters
  • Installation
  • Terminal Introduction
  • Wiring Diagrams
  • Operation Guide

Specifications

Normal operating temperature-10℃ to 50℃
Limit operating temperature-20℃ to 60℃
Storage temperature-40℃ to 85℃
Relative humidity5% to 90%
Working power supply voltage rangeAC/DC 60V to 250V
Working power supply frequency range45Hz to 55Hz
Normal power consumptionLess than 4W
AC voltage circuit rated voltage380V/100V
Measurement accuracyClass 1
Relay output breaking capacity10A/250VAC, 10A/30VDC
Digital input collectionUp to 8 channels
Mounting35mm standard DIN rail or screw fixing

Frequently asked questions

What is the DCM-631 series used for?

It is a low-voltage power automatic switching device used in distribution systems below 690V to switch quickly and reliably between main and backup power supplies.

How is the DCM-631 device mounted?

It can be mounted on a 35mm standard DIN rail or fixed with screws through the positioning holes; a split version mounts the display module on the cabinet door.

Which communication interface does the device have?

It has a standard RS-485 interface using the Modbus protocol, allowing connection to a monitoring system over a twisted-pair network.

Which model is used for a dual power supply system?

DCM-631Z is for dual power supply systems, with automatic switching and restoration, automatic switching without restoration, or two incomings as mutual backup.

Download PDF (1.6 MB)

More GODGOAL Manuals


View all GODGOAL manuals →