User manual for the GODGOAL DCM611 low‑voltage line monitoring and protection device, covering installation, operation, and specifications.
The DCM‑611 series is a low‑voltage line monitoring and protection device for systems below 690 V. It provides over‑current, short‑circuit, over‑voltage, under‑voltage, ground‑fault, imbalance and overload protection, together with three‑phase power measurement, digital I/O and network communication.
The manual describes hardware configuration, installation methods, operation procedures, protection functions and communication protocols (RS‑485 Modbus). It also lists technical parameters, ordering information and wiring guidelines. This manual is written in Chinese.
| Rated Voltage | 100 V / 380 V |
|---|---|
| Current Rating | 5 A, 1 A |
| Continuous Overload Capacity | 1.2 × rated |
| Non‑continuous Overload Capacity | 2500 V / 1 s |
| Power Supply | AC/DC 60 V‑265 V |
| Power Consumption | < 5 W |
| Operating Temperature | -20 °C ~ 60 °C |
| Storage Temperature | -40 °C ~ 75 °C |
| Dimensions (device body) | 126 mm × 102 mm × 6 mm |
| Digital Input Channels | 8 isolated inputs |
| Digital Output Channels | Up to 7 relay outputs |
| Communication Interface | RS‑485, Modbus, 4800‑19200 bps |
The device provides up to 8 isolated digital input channels.
It uses an RS‑485 interface with the Modbus protocol, supporting 4800‑19200 bps.
Install a surge suppressor in the power circuit when the device is used in areas with poor power quality.
A 1 A fuse or circuit breaker is recommended at the device power input.