MSpower DVR low voltage crossing device instruction manual, mainly used in petrochemical, steel, intelligent manufacturing and other industries, can be used for motor safety power supply, has strong anti-interference ability, can be used in power supply voltage surge, sag, voltage interruption and overvoltage, for power equipment to provide a perfect protection scheme
The MSpower DVR is a low voltage ride-through device from Nanjing GODGOAL-ELECTRIC Automation, described as a safety power supply for 400 V motors in petrochemical, steel and intelligent-manufacturing applications. It supports continuous motor operation during grid voltage disturbances and short interruptions using a supercapacitor energy storage unit, an inverter and a static switch that transfers back to the grid when voltage recovers.
The document covers user notices, main features, models and configuration, device principle, technical specifications, system structure, operating modes, installation and commissioning, and front-panel functions. Available models are MSpower DVR-20, MSpower DVR-50, MSpower DVR-100 and MSpower DVR-150, with 20, 50, 100 and 150 kW system capacities and a 5-second ride-through time. This manual is written in Chinese.
| Rated capacity | 20, 50, 100, 150 kVA |
|---|---|
| Grid rated voltage | 220 V ±10%, settable |
| Grid frequency | 50 Hz ±5 Hz |
| Overload capability | 110% load continuous; 120% load protected for 10 min; >120% load protected for 200 ms (linear load) |
| Transfer time | Typical 2 ms |
| Maximum supply time | 5 s |
| System DC voltage | 540 VDC |
| Energy storage type | Supercapacitor / high-rate battery |
| Enclosure protection rating | IP40 |
| Operating temperature | -20 °C to 45 °C |
| Humidity | <95%, non-condensing |
| Noise | <70 dB |
| Communication interface | RS485, Ethernet |
The maximum supply time is 5 s.
The typical transfer time is 2 ms.
The usual energy storage unit is a supercapacitor module.
The bypass contactor is closed and an alarm output is given.