This document is the installation and setup guide, which introduces how to connect ATS1745 IP-LAN adapter.
The ATS1745 IP-LAN Adapter carries ATS data over an IP network and converts it back to RS-485 communications for connection to bus devices such as a remote arming station (RAS) or a data gathering panel (DGP). Modules work in pairs as either a start-of-line module (SLM) or an end-of-line module (ELM), and provide encrypted IP communications using a unique 128-bit encryption key. One SLM can be connected to as many as 31 ELMs.
This installation and setup guide describes the module layout, LED indications, DIP switch settings and the onboard Web interface used by installers to configure parameters such as assigned IP addresses. It also covers installation requirements, connecting the module, system setup, enabling communications, updating firmware, managing users, diagnostics and troubleshooting, and ends with specifications and a network assignments worksheet.
| Operating power | 13.8 VDC supplied by the panel |
|---|---|
| Operating current (typical) | 110 mA |
| Operating temperature | 0 to 40°C |
| Maximum relative humidity | 93 % |
| Dimensions (PCB) (W x H x D) | 50 x 80 x 20 mm |
| Weight (PCB) | 31 g |
An SLM can be connected to as many as 31 ELMs, providing IP connections to each bus's RASs and DGPs.
The connection to one or more ELMs is too slow, meaning a one-way latency of more than 20 ms.
They are powered by 13.8 VDC supplied by the panel, drawing a typical operating current of 110 mA.
Set DIP switch SW3 to ON for disable Web server; OFF keeps Web programming mode.