UTC Fire & Security Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

This is the Alarmline II Analogue Linear Heat Sensor Cable Technical Manual user manual, which applies to the following models: AA AAN AAP AASS AASSN AACULP AACUSP


UTC Fire & Security Alarmline II Analogue Linear Heat Sensor Cable Technical Manual - cover page
Brand
UTC Fire & Security
Category
Monitoring Equipment
Document type
User Manual
Language
English
Pages
51
File format
PDF
File size
2.9 MB
Published
01 November, 2023
Updated
01 November, 2023
MD5 checksum
B88A7C50F47450B7F9D5DB47FC676A59

About this manual

Alarmline II Analogue linear heat detection systems use sensor cable with temperature-sensitive polymer cores and a control unit that monitors resistance changes to trigger pre-alarm or alarm conditions. The manual covers the product range, approvals, technical specifications, design and installation guidelines, commissioning and application guidelines.

The sensor cable is available with several protective outer sheaths, and the control unit provides volt-free relay outputs and an opto-isolated fault output for interfacing with fire alarm control systems.

What's inside

  • Introduction
  • Operation
  • Product range
  • Approvals
  • Technical Specifications
  • Design and installation
  • Jointing
  • Hazardous area installation
  • Commissioning
  • Application guidelines

Specifications

Outer jacketHigh temperature red PVC
Sensor cable diameter4.57mm ± 0.075mm (0.180" ± 0.003")
Maximum sensor cable length500m (1640ft)
Minimum sensor cable length30.5m (100ft)
Sensor cable operating temperature range-40ºC to 125ºC (-40°F to 257°F)
Continuous ambient temperature range-40ºC to 90ºC (-40°F to 194°F)
Control unit dimensions (w x h x d)182 x 180 x 90mm (7.2" x 7.1" x 3.5")
Control unit enclosure ratingIP66 (IK08)
Control unit supply voltage20-28 VDC
Alarm/pre-alarm temperature range54ºC to 100ºC (129ºF to 212ºF)

Frequently asked questions

What is the maximum length of Alarmline II sensor cable?

The maximum sensor cable length is 500 m (1640 ft).

What supply voltage does the control unit require?

The control unit requires a supply voltage of 20-28 VDC.

What is the control unit enclosure rating?

The control unit enclosure is rated IP66 (IK08).

What is the approved UL spacing for the sensor cable?

The approved UL spacing for the sensor cable is 10 m (35 ft).