Teren TCL-xA / TCL-xA-W Low Temperature Controller User Manual

TCL Low Temperature Controller User Manual, including product application features, technical indexes, selection table, wiring/function diagram, installation, and precautions.


Teren TCL-xA / TCL-xA-W Low Temperature Controller User Manual - cover page
Brand
TEREN
Category
Temperature monitor
Document type
User Manual
Language
Chinese
Pages
2
File format
PDF
File size
362 KB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
74B5DEB14FF789AA3FD5D0787324F5E9

About this manual

Teren's TCL low temperature controller manual describes the TCL-xA and TCL-xA-W controllers, which use a copper capillary sensing element and an SPDT switch that opens as temperature falls. The TCL-xA setting range is 0 to 7 °C; the TCL-xA-W range is -14 to 12 °C. Models are available with 1.5 m, 3 m, or 6 m capillary lengths.

The document lists technical data, a model selection table, and a wiring and function diagram. It explains wall mounting with 3 mm holes and self-tapping screws, and gives installation precautions for the controller and capillary, including keeping the capillary length on a cold coil longer than 20 cm and not crushing it. This manual is written in Chinese.

What's inside

  • Applications and Features
  • Technical Specifications
  • Model Selection Table
  • Wiring / Function Diagram
  • Installation
  • Installation Precautions
  • Note
  • Wiring Diagram
  • Capillary Installation Diagram
  • Controller Installation Diagram

Specifications

Setting temperature range (TCL-xA)0 to 7 °C
Setting temperature range (TCL-xA-W)-14 to 12 °C
Sensing elementCopper capillary, Φ2 mm diameter
Switch operating environment-10 to 70 °C, <95% RH, non-condensing
Sensing element operating temperature range-30 to 80 °C
AccuracyTypical ±2 °C
Switch outputSPDT, opens on temperature fall
Contact capacity250 VAC/5 A non-inductive; 250 VAC/4 A inductive
Electrical connection3 screw terminals, 1.5 mm² wire, PG9
Electrical strengthAC 1500 V for 1 min (AC 1800 V for 1 s)
Insulation resistance≥100 MΩ normal; ≥10 MΩ damp
Protection ratingIP54

Frequently asked questions

What temperature range does the TCL-xA controller support?

The TCL-xA setting range is 0 to 7 °C; the TCL-xA-W setting range is -14 to 12 °C.

How do the switch contacts behave when the temperature drops to the set point?

Terminals 2 and 3 open, and terminals 2 and 1 close. When the temperature rises above the set point by the differential, 2 and 3 reconnect.

What is the controller's protection rating?

The protection rating is IP54.

How long should the capillary be coiled on a cold coil for reliable operation?

The capillary length on the cold coil should be longer than 20 cm.

Download PDF (362 KB)