TCL Low Temperature Controller User Manual, including product application features, technical indexes, selection table, wiring/function diagram, installation, and precautions.
Teren's TCL low temperature controller manual describes the TCL-xA and TCL-xA-W controllers, which use a copper capillary sensing element and an SPDT switch that opens as temperature falls. The TCL-xA setting range is 0 to 7 °C; the TCL-xA-W range is -14 to 12 °C. Models are available with 1.5 m, 3 m, or 6 m capillary lengths.
The document lists technical data, a model selection table, and a wiring and function diagram. It explains wall mounting with 3 mm holes and self-tapping screws, and gives installation precautions for the controller and capillary, including keeping the capillary length on a cold coil longer than 20 cm and not crushing it. This manual is written in Chinese.
| Setting temperature range (TCL-xA) | 0 to 7 °C |
|---|---|
| Setting temperature range (TCL-xA-W) | -14 to 12 °C |
| Sensing element | Copper capillary, Φ2 mm diameter |
| Switch operating environment | -10 to 70 °C, <95% RH, non-condensing |
| Sensing element operating temperature range | -30 to 80 °C |
| Accuracy | Typical ±2 °C |
| Switch output | SPDT, opens on temperature fall |
| Contact capacity | 250 VAC/5 A non-inductive; 250 VAC/4 A inductive |
| Electrical connection | 3 screw terminals, 1.5 mm² wire, PG9 |
| Electrical strength | AC 1500 V for 1 min (AC 1800 V for 1 s) |
| Insulation resistance | ≥100 MΩ normal; ≥10 MΩ damp |
| Protection rating | IP54 |
The TCL-xA setting range is 0 to 7 °C; the TCL-xA-W setting range is -14 to 12 °C.
Terminals 2 and 3 open, and terminals 2 and 1 close. When the temperature rises above the set point by the differential, 2 and 3 reconnect.
The protection rating is IP54.
The capillary length on the cold coil should be longer than 20 cm.