This manual introduces the quick calibration and troubleshooting methods of TDC-100 series AC digital high-resolution controller
This guide provides quick calibration and troubleshooting instructions for the AT Controls TDC-100 Series AC Digital High-Resolution Controller. It explains how to use the MODE and adjust buttons to set operating modes and calibrate the actuator.
The document also covers auxiliary open/close and position output setup for optional modules, command type selection, loss of command behavior, and fault indicator meanings for conditions such as motor stall, feedback alarm, and command out of range.
| Input signal types | 4-20mA, 1-5VDC, 0-5VDC, 0-10VDC, 2-10VDC, or Digital |
|---|---|
| Feedback alarm range | Less than 5% or more than 95% of potentiometer value |
| Stall fault clearance motion | Greater than 1.5 degrees in either direction |
The controller supports 4-20mA, 1-5VDC, 0-5VDC, 0-10VDC, 2-10VDC, or Digital input signals.
The fault clears when the TDC-100 detects actuator motion greater than 1.5 degrees in either direction, such as through a command signal, manual adjust buttons, or mechanical override.
A Feedback Alarm occurs when the feedback signal is below 5% or above 95% of the potentiometer value, or when potentiometer connections are broken.