This manual introduces the installation and maintenance methods of EPR electro-pneumatic positioner.
This manual provides instructions for the installation and maintenance of the A-T Controls EPR Series Electro-Pneumatic Positioner. It details the principle of operation, where a torque motor converts electrical signals into pneumatic output to move a cylinder actuator via a feedback loop involving a nozzle and flapper.
The document covers standard mounting methods, including fork lever and direct NAMUR mounting, along with procedures for cam and indicator adjustment. It also explains how to perform zero and span adjustments, adjust the pilot valve seat for double-acting actuators, and switch between automatic and manual operation.
| Input Signal | 4~20mA |
|---|---|
| Input Voltage | 24VDC |
| Air Supply Pressure | Max. 100 PSI |
| Standard Stroke | 60º ~ 100º |
| Air Piping Connection | ¼” NPT |
| Conduit Connection | ½” NPT |
| Explosion-Proof Classification | ExmdⅡBT6, ExmdⅡC(H2)T6, IP66, Exia ⅡBT6 |
| Ambient Temperature | -4 ~ 158 Deg F |
| Linearity | Within ± 1.5 % F.S |
| Sensitivity | Within 0.5 % F.S |
| Hysteresis | Within 1.0% F.S |
| Repeatability | Within ± 0.5 % F.S |
| Air Consumption | 0.18 CFM (Sup. 20PSI) |
| Flow Capacity | 2.83 CFM (Sup. 20PSI) |
| Body Weight | 6.40 Lbs (with a terminal box) |
The standard stroke is adjustable between 60º and 100º, though it can be adjusted to 0º ~ 60º or 0º ~ 100º.
The zero point is adjusted by changing the zero adjustment spring tension.
Hunting can be caused by a small actuator requiring orifice restrictions, a clogged nozzle, or an unstable air supply.
Set the Auto / Manual switch located on the pilot valve to M to bypass the 4 ~20mA input signal.