This manual describes the safety features of the IQ T series electric valve actuators, including application range, safety functions, safety function operation, design requirements and other contents.
The Rotork IQ Range IQ3 Safety Manual covers IQ multi-turn electric valve actuators fitted with the optional Safety Function Control Board. It defines setup, installation, operation, commissioning, verification and maintenance for actuators used in Safety Instrumented Systems requiring SIL 2 or SIL 3 to IEC 61508-2:2010.
The manual describes Safety Function 1 (Stayput), where the actuator must not move spuriously, and Safety Function 2 (ESD), where it moves on demand. It states that both functions require hardwired Motor Enable and ESD signals in the 14–60 VDC range, and that IQ3 actuators for these functions must use a three-phase supply. It also references SIRA certificate FSP 15001 and requires use with PUB002-039, the IQ3 Safe Use, Installation and Maintenance manual.
| Power supply | Three-phase electrical supply only |
|---|---|
| Operating temperature | -30 to 70 °C standard; low temperature options down to -40 °C |
| Enclosure rating | IP66 and IP68 to IEC60529 |
| Safety function control signal range | 14–60 VDC hardwired signals |
| Functional safety integrity | SIL 2 or SIL 3 to IEC 61508-2:2010 |
| Approval certificate | SIRA FSP 15001 |
| SIL capability for Safety Function 2 with PVST | SIL 2 (low demand, HFT=0) |
Safety Function 1 is a high-demand mode function in which the actuator shall not move without a valid Motor Enable signal combined with a valid remote Open, Close or ESD signal.
Safety Function 2 is a low-demand mode function in which the actuator operates as configured (Open, Close or Stayput) with a valid ESD control signal.
Yes. They may be combined with either one configured to have priority.
IQ3 actuators for the safety functions must be powered by a three-phase electrical supply only.