Rotork IQ Range IQ3 Electric Valve Actuators Safety Manual Including Safety Function Control Board Option

This manual describes the safety features of the IQ T series electric valve actuators, including application range, safety functions, safety function operation, design requirements and other contents.


Rotork IQ Range IQ3 Electric Valve Actuators Safety Manual Including Safety Function Control Board Option - cover page
Brand
Rotork
Category
Automation control Equipment
Document type
Service Manual
Language
English
Pages
32
File format
PDF
File size
2.4 MB
Published
31 October, 2023
Updated
31 October, 2023
Model
IQ3
MD5 checksum
64287FDE47C5538BE2583CCA2AE70A68

About this manual

The Rotork IQ Range IQ3 Safety Manual covers IQ multi-turn electric valve actuators fitted with the optional Safety Function Control Board. It defines setup, installation, operation, commissioning, verification and maintenance for actuators used in Safety Instrumented Systems requiring SIL 2 or SIL 3 to IEC 61508-2:2010.

The manual describes Safety Function 1 (Stayput), where the actuator must not move spuriously, and Safety Function 2 (ESD), where it moves on demand. It states that both functions require hardwired Motor Enable and ESD signals in the 14–60 VDC range, and that IQ3 actuators for these functions must use a three-phase supply. It also references SIRA certificate FSP 15001 and requires use with PUB002-039, the IQ3 Safe Use, Installation and Maintenance manual.

What's inside

  • Overview
  • Safety Functions
  • Safety Function Operation
  • Design Requirements
  • Installation
  • General Safety Function Commissioning
  • Verification
  • Tamper Prevention
  • General Maintenance

Specifications

Power supplyThree-phase electrical supply only
Operating temperature-30 to 70 °C standard; low temperature options down to -40 °C
Enclosure ratingIP66 and IP68 to IEC60529
Safety function control signal range14–60 VDC hardwired signals
Functional safety integritySIL 2 or SIL 3 to IEC 61508-2:2010
Approval certificateSIRA FSP 15001
SIL capability for Safety Function 2 with PVSTSIL 2 (low demand, HFT=0)

Frequently asked questions

What is Safety Function 1 (Stayput) on the IQ actuator?

Safety Function 1 is a high-demand mode function in which the actuator shall not move without a valid Motor Enable signal combined with a valid remote Open, Close or ESD signal.

What is Safety Function 2 (ESD)?

Safety Function 2 is a low-demand mode function in which the actuator operates as configured (Open, Close or Stayput) with a valid ESD control signal.

Can Safety Functions 1 and 2 be combined?

Yes. They may be combined with either one configured to have priority.

What power supply do IQ3 actuators need for the safety functions?

IQ3 actuators for the safety functions must be powered by a three-phase electrical supply only.

Download PDF (2.4 MB)

More Rotork Manuals