Key facts
- Brand
- Rotork
- Model
- IQ3
- Category
- Automation control Equipment
- Documents
- 3
- Languages
- EN
- Last added
- 2026-11-15
Start here

Rotork IQ3 Range Wiring Manual
The document serves as a manual for the Rotork IQ3 range, specifically focusing on wiring configurations. It includes diagrams and guidance necessary for connecting the device correctly.
The text also contains a standard website cookie notice explaining the use of essential cookies for site operation and non-essential analytics cookies for improving user experience.
Rotork IQ3 specifications
| Enclosure | IP66 /IP68 - 20 metres/10 days |
|---|---|
| Temperature | -20° C to 70° C (-22° F to 158° F) |
| Motor | Three phase low inertia squirrel cage motor, class F insulation |
| Service/Duty Rating | Class A (On/Off), Class B (Inching) |
| Starter | Integral electrically and mechanically interlocked reversing contactors |
| Local Indication | Integral illuminated, digital valve position indicator |
| Position Sensor | Absolute encoder |
| Cable Entries | 2x M25 + 1x M40 |
Source: Rotork IQ3 Multi-Turn Three Phase Electric Actuator Specification
All Rotork IQ3 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Disassembly, diagnostics and part numbers, for repair.
Questions answered in these manuals
What enclosure rating does the Rotork IQ3 have?
It is watertight to IEC/BS EN 60529, IP66/IP68 for 20 metres/10 days.
From: Rotork IQ3 Multi-Turn Three Phase Electric Actuator Specification
What is the operating temperature range of the IQ3 actuator?
The temperature range is -20°C to 70°C (-22°F to 158°F), subject to hazardous area certification.
From: Rotork IQ3 Multi-Turn Three Phase Electric Actuator Specification
What is Safety Function 1 (Stayput) on the IQ actuator?
Safety Function 1 is a high-demand mode function in which the actuator shall not move without a valid Motor Enable signal combined with a valid remote Open, Close or ESD signal.
What is Safety Function 2 (ESD)?
Safety Function 2 is a low-demand mode function in which the actuator operates as configured (Open, Close or Stayput) with a valid ESD control signal.