This document is a Kohler faucet installation manual, which mainly introduces installation, maintenance, cleaning and other contents.
This Kohler installation guide covers the 98149T two-way and 98150T three-way recessed thermostatic valve cartridges. It lists supply pressure and hot water temperature requirements, rough-in dimensions, and notes to check for leaks before covering the pipes.
The document explains how to install the valve body, connect G1/2 hot and cold supplies, shower and bath pipes, set and verify the outlet temperature at 37°C, and operate the temperature and diverter handles. It also gives cleaning steps for the thermostatic cartridge and for the check valve and filter kits. This manual is written in Chinese.
| Minimum supply pressure | 0.5 bar (0.05 MPa) |
|---|---|
| Recommended supply pressure | 3 bar (0.3 MPa) on hot and cold water |
| Maximum hot/cold pressure difference | 2 bar (0.2 MPa) |
| Hot supply water temperature | Minimum 50°C, maximum 70°C |
| Recommended hot supply water temperature | 60°C |
| Temperature setting range | Approximately 20°C to 50°C |
| Safety stop temperature | 40°C |
| Pressure reducer requirement | Install if supply pressure is higher than 5 bar |
| Water pressure test limit | Below 0.8 MPa (8 bar), within 30 minutes |
The minimum supply pressure is 0.5 bar (0.05 MPa).
A pressure reducer should be installed.
The safety stop temperature is 40°C.
It is removed cautiously and cleaned by soaking it in warm vinegar.