IM3319/3320 Three-Phase Mutual Inductance Power Quality Detector Product Manual

IM3319/3320 three-phase mutual inductance energy quality detector product manual, introduces the product's functions, features, technical parameters, application instructions and other contents


IM3319/3320 Three-Phase Mutual Inductance Power Quality Detector Product Manual - cover page
Category
Monitoring Equipment
Document type
User Manual
Language
Chinese
Pages
8
File format
PDF
File size
865 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
7800E07C5020B394A1B066CA487F8654

About this manual

The IM3319/3320 is a three-phase mutual inductance power quality detector that measures voltage, current, power, power factor, energy and total energy in 50 Hz or 60 Hz three-phase AC networks. It has two RS-485 interfaces, an optional digital output, an external LCD display port and Modbus-RTU communication.

The manual documents product introduction, features, technical parameters, installation, terminal definitions, typical wiring, application notes, Modbus registers and Modbus communication protocol. It also lists factory default settings and RS-485 network connection guidance. This manual is written in Chinese.

What's inside

  • Product Introduction
  • Functions and Features
  • Technical Parameters
  • Appearance and Installation
  • Terminal Definitions
  • Typical Wiring
  • Application Notes
  • Modbus Register List
  • Modbus Communication Protocol
  • Precautions

Specifications

Voltage range100 V, 220 V, 380 V and other options
Current range5 A, 20 A, 50 A, 100 A, 200 A, 300 A, 400 A, 500 A and other options
Signal processingDedicated measurement chip, 24-bit AD sampling
Continuous overload1.2 times range continuous
Short-time overloadCurrent 5 times and voltage 2 times range for <200 mS without damage
Input impedanceVoltage channel >1 kΩ/V; current channel ≤100 mΩ
Digital output1 channel relay open-collector output with voltage and current overload alarm protection output
Communication interfaceTwo RS-485 interfaces
Communication protocolMODBUS-RTU
Data formatn,8,1; e,8,1; o,8,1; n,8,2, software configurable
Baud rateRemote RS-485 configurable 1200, 2400, 4800, 9600 bps; local RS-485 fixed at 4800 bps
Measurement accuracyVoltage, current and power ±1.0%; active energy class 1
Isolation voltage2000 VDC
Power supply100 V, 220 V, 380 V; voltage line 100 V–380 V; DC +5 V
Power consumption≤2 W typical
Operating temperature-20 to +60 °C; storage -40 to +85 °C
Relative humidity5 to 95%, non-condensing at 40 °C
Altitude0 to 3000 m
Temperature drift≤100 ppm/°C
Mounting35 mm standard DIN rail or screw fixing with 104 × 70 mm hole spacing
Dimensions116 × 94 × 58 mm

Frequently asked questions

What parameters does the detector measure?

It can provide three-phase voltage, current, power, power factor, active energy and carbon emissions.

Which communication protocol does the detector use?

It uses the standard Modbus-RTU protocol.

What are the factory default settings?

The default address is 1, baud rate is 4800 bps, data format is n,8,1, data update rate is 1000 ms and ratio is 1.

How is the module installed?

It can be mounted on a 35 mm standard DIN rail or fixed with screws using 104 × 70 mm mounting hole spacing.

Download PDF (865 KB)