Invensys SRP981 Pneumatic Positioner Quick Guide

Pneumatic Positioner Quick Guide


Invensys SRP981 Pneumatic Positioner Quick Guide - cover page
Brand
invensys
Category
Electro-Pneumatic Positioner
Document type
Quick Start Guide
Language
Chinese
Pages
16
File format
PDF
File size
884 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
3B4A6316900DC913B8227FB6CCF3D8B8

About this manual

This quick guide for the Invensys SRP981 pneumatic positioner is provided in Chinese and English. It covers mounting to linear and rotary actuators, pneumatic connections, optional electrical connections, limit switches, and the optional 4–20 mA position transmitter.

Setup instructions describe zero and stroke adjustment, damping adjustment, and position transmitter calibration. A spring range table lists available stroke ranges, and the guide refers readers to the Master Instructions and Product Specification Sheet for more detail. This manual is written in Chinese.

What's inside

  • Mounting to Linear Actuators
  • Mounting to Rotary Actuators
  • Pneumatic Connections
  • Optional Electrical Connections
  • Optional Limit Switch
  • Optional Position Transmitter 4-20 mA
  • Setup and Start-Up
  • Setting Zero and Stroke
  • Setting Damping
  • Spring Ranges

Specifications

Supply air pressure1.4 to 6 bar
Pneumatic connectionG 1/8 internal thread for supply air
Analog output4 to 20 mA, two-wire
Transmitter supply voltageDC 11 to 48 V
Position transmitter calibration current range3.3 mA to 22.5 mA

Frequently asked questions

What air supply does the SRP981 require?

The air supply is 1.4 to 6 bar and must not exceed the actuator's maximum pressure; it must be free of oil, dust and water.

How are zero and stroke set?

Adjust the zero screw until the actuator starts to move from its zero point, then adjust the stroke screw until it reaches the end position, and repeat two to three times.

What output does the optional position transmitter provide?

It provides a standard 4–20 mA two-wire analog output with a DC 11 to 48 V supply.

Download PDF (884 KB)