Young Tech YT-3300 / 3350 / 3303 / 3301 Series Smart Valve Positioner Product Manual

This document is the user manual of YT-3300 / 3350 / 3303 / 3301 series


Young Tech YT-3300 / 3350 / 3303 / 3301 Series Smart Valve Positioner Product Manual - cover page
Brand
Young Tech
Category
Electro-Pneumatic Positioner
Document type
User Manual
Language
English
Pages
78
File format
PDF
File size
6.3 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
D3DAAD292F4B00EF69678F9408697505

About this manual

The YT-3300 / 3350 / 3303 / 3301 series Smart Valve Positioner controls valve stroke in response to a 4~20mA input signal from the controller. A built-in microprocessor supports auto-calibration, PID control and HART protocol communications, and the LCD display lets users monitor positioner status. The manual covers product description, specifications, dimensions, certifications and parts.

Installation sections cover linear and rotary positioners, air piping for single- and double-acting actuators, power connection and grounding. Adjustment and operation sections describe limit switch and A/M switch adjustment, optional sub-PCB installation, auto calibration, manual and parameter modes, valve settings, diagnostics and error/warning codes.

What's inside

  • Introduction
  • Product Description
  • Installation
  • Connection – Air
  • Connection – Power
  • Adjustments
  • Optional Sub-PCB Installment
  • Auto Calibration and PCB Operation
  • Error and Warning Code
  • Main Software Map

Specifications

Input signal4~20mA
Protection gradeIP66, Type 4X(FM)
Operating temperature (positioners)-30 ~ 85℃ or -40 ~ 85℃
Operating temperature (YT-3301 sensor module)-40 ~ 120℃
Split range4~12mA or 12~20mA
Valve flow characteristicsLinear, Quick Open, Equal Percentage, and Custom

Frequently asked questions

What input signal does the smart positioner use?

It uses a 4~20mA input signal from the controller.

What is the manufacturer warranty period?

The product is warranted for eighteen (18) months from the date of original purchase.

What protection grade does the positioner have?

It has IP66 and Type 4X(FM) protection.

Can the split range be changed?

Yes, a split range of 4~12mA or 12~20mA can be set.