This manual only describes the installation of outdoor unit. When installing the indoor unit, refer to the installation manual of indoor unit. Any structural alterations necessary for installation must comply with local build- ing code requirements.
This manual describes the installation of the outdoor unit of the MXZ-2C20NA3 split-type air-conditioner. It is addressed to the installer and does not cover the indoor unit, whose installation is described in the indoor unit's own manual. The pages supplied here open with the safety rules that must be observed before any work, list the tools required for installation, and give a specification table for the model.
The contents run from before installation through outdoor unit installation, flaring work and pipe connection, purging procedures, leak test and test run, and pumping down. The unit uses R410A refrigerant, and the manual notes that only the specified refrigerant may enter the refrigerant circuit. The document is printed with English, French and Spanish sections.
| Model | MXZ-2C20NA3 |
|---|---|
| Power supply | 208 / 230 V, 60 Hz |
| Max. pipe length per indoor unit / for multi-system | 82 ft. (25 m) / 164 ft. (50 m) |
| Max. height difference | 49 ft. (15 m) |
| Refrigerant | R410A |
| Refrigerant adjustment A | 1.08 oz each 5 ft. (20 g/m) |
| Additional charge threshold | Pipe length exceeding 131.2 ft. (40 m) |
| Refrigerant pipe bending radius | 4 in. (100 mm) or more |
The system is specified for R410A refrigerant. No substance other than R410A may enter the refrigerant circuit.
The maximum pipe length is 82 ft. (25 m) per indoor unit, or 164 ft. (50 m) for a multi-system, and the maximum height difference is 49 ft. (15 m).
An additional R410A charge is required when the pipe length exceeds 131.2 ft. (40 m); no additional charge is needed below that length.
No. It only describes the installation of the outdoor unit; for the indoor unit you must refer to the indoor unit's installation manual.