MXZ-2C20NA3 Split-type Air-Conditioner Outdoor Unit Installation Manual

This manual only describes the installation of outdoor unit. When installing the indoor unit, refer to the installation manual of indoor unit. Any structural alterations necessary for installation must comply with local build- ing code requirements.


MXZ-2C20NA3 Split-type Air-Conditioner Outdoor Unit Installation Manual - cover page
Category
Air conditioner
Document type
Installation Guide
Language
English
Pages
24
File format
PDF
File size
1.6 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
A80911AC4AF68D13B8EF534E4580F617

About this manual

This manual describes the installation of the outdoor unit of the MXZ-2C20NA3 split-type air-conditioner. It is addressed to the installer and does not cover the indoor unit, whose installation is described in the indoor unit's own manual. The pages supplied here open with the safety rules that must be observed before any work, list the tools required for installation, and give a specification table for the model.

The contents run from before installation through outdoor unit installation, flaring work and pipe connection, purging procedures, leak test and test run, and pumping down. The unit uses R410A refrigerant, and the manual notes that only the specified refrigerant may enter the refrigerant circuit. The document is printed with English, French and Spanish sections.

What's inside

  • Safety precautions
  • Required tools for installation
  • Specifications
  • Before installation
  • Outdoor unit installation
  • Flaring work and pipe connection
  • Purging procedures, leak test, and test run
  • Pumping down

Specifications

ModelMXZ-2C20NA3
Power supply208 / 230 V, 60 Hz
Max. pipe length per indoor unit / for multi-system82 ft. (25 m) / 164 ft. (50 m)
Max. height difference49 ft. (15 m)
RefrigerantR410A
Refrigerant adjustment A1.08 oz each 5 ft. (20 g/m)
Additional charge thresholdPipe length exceeding 131.2 ft. (40 m)
Refrigerant pipe bending radius4 in. (100 mm) or more

Frequently asked questions

What refrigerant does the MXZ-2C20NA3 use?

The system is specified for R410A refrigerant. No substance other than R410A may enter the refrigerant circuit.

What is the maximum pipe length and height difference?

The maximum pipe length is 82 ft. (25 m) per indoor unit, or 164 ft. (50 m) for a multi-system, and the maximum height difference is 49 ft. (15 m).

When is an additional refrigerant charge required?

An additional R410A charge is required when the pipe length exceeds 131.2 ft. (40 m); no additional charge is needed below that length.

Does this manual cover the indoor unit?

No. It only describes the installation of the outdoor unit; for the indoor unit you must refer to the indoor unit's installation manual.