COM100 intelligent communication box is a smart communication box developed and produced by Sungrow Power Supply Co., Ltd. It integrates optical fiber switches, optical fiber terminal boxes and other equipment. It is easy to network and supports various protocols to meet the needs of various application scenarios.
This user manual from Sungrow (阳光电源股份有限公司) describes the COM100 intelligent communication box (COM100-V22-UCN-Ver12) and is written for professional technicians who install and operate it. It explains the purpose and intended readers of the manual, then describes the product's functions and main features: an integrated fiber switch and fiber terminal box for flexible networking, an integrated data logger for local intelligent commissioning, wall, pole and floor mounting options, built-in PLC communication for the company's own string inverters without extra cabling, integration with the Sungrow cloud, electrical isolation and lightning protection, and an IP65 rating for long-term outdoor operation.
Mechanical installation covers pre-installation checks against the packing list, site requirements and the wall-mounted and floor-mounted methods, with pole mounting offered as an option. Electrical connection covers the waterproof terminals, internal structure, grounding, RS485 communication terminals, optional fiber access, AC wiring and PLC port wiring. Commissioning steps, a troubleshooting table, technical specifications and warranty and contact information complete the manual. This manual is written in Chinese.
| Data logger | Logger3000 |
|---|---|
| Fiber switch (optional) | 2 optical, 6 electrical fiber switch |
| Power supply | 100~277 Vac, 50/60 Hz |
| PLC port input voltage | 400 Vac / 480 Vac / 540 Vac / 800 Vac |
| Power consumption | Average 30 W, maximum 40 W |
| Operating temperature | -25 °C to +60 °C |
| Operating humidity | 0~95%, non-condensing |
| Protection rating | IP65 |
| Dimensions (W x H x D) | 570 x 790 x 190 mm |
| Weight | 32 kg |
| Mounting methods | Pole mounting, floor mounting, wall mounting |
| Cable entry | Bottom inlet, bottom outlet |
The COM100 has an IP65 protection rating, so it can be installed either indoors or outdoors, and it is normally installed outdoors.
Wall mounting and floor mounting are the two common methods; pole mounting is a third, optional solution that can be requested when ordering.
The M10 hex bolt assemblies are tightened to 37±3 N.m.
Possible causes listed are an RS485 cable fault, duplicate device addresses in the array, incorrect data logger parameter configuration, or an abnormal PLC master/slave node module.