The manual introduces the applications and features of the frequency relay XF2, as well as the design, function, operation and setting, relay case and technical data of the product.
The SEG Electronics XF2 is a digital measuring relay from the PROFESSIONAL LINE designed for frequency supervision of single- and three-phase AC voltages. It provides reliable protection against inadmissible over- and underfrequency with high measuring accuracy and extremely short response times. Key features include fault indication via LEDs, a wide operating range for supply voltages, and the ability to exchange data with process management systems via a serial interface adapter.
| Rated voltage | 100, 110, 230; 400 V AC |
|---|---|
| Rated frequency | 50 / 60 Hz |
| Frequency measuring range | 35 - 78 Hz |
| Auxiliary voltage range (AC) | 36 - 520 V AC |
| Auxiliary voltage range (DC) | 50 - 750 V DC |
| Temperature range | -25°C to +70°C |
| Degree of protection | IP40 |
| Weight | approx. 0.5 kg |
The frequency measuring range is 35 - 78 Hz.
Yes, the unit can be set to fn=50 Hz or fn=60 Hz using DIP-switch 6.
The rated voltage (100, 110, 230, or 400 V) is set using DIP-switches 1, 2, and 3.
Supervision of the frequency is blocked if the measuring voltage drops below 70% Un.