This manual covers the operation, settings, testing, and technical data for the SEG Electronics MRQ1 Field Failure Relay used to protect synchronous generators.
The SEG Electronics MRQ1 is a digital protection relay designed specifically for field failure (loss of excitation) protection in synchronous generators. It detects low or under impedance conditions caused by partial or complete loss of excitation, which can lead to out-of-step operation and system instability. The device calculates momentary impedance values from generator current and voltage, comparing them against two separate under-impedance elements with distinct settings for steady-state and dynamic stability areas.
The relay protects synchronous generators against operation outside the stable area caused by a loss of excitation.
The calculation uses line-to-line voltage U23 and phase current L1.
Connecting the auxiliary voltage to the blocking input inhibits all protective functions of the MRQ1.