SEG Electronics MRL1 Lock-Out Relay User Manual

This manual covers the installation, operation, testing, and technical specifications of the SEG Electronics MRL1 Lock-Out Relay.


SEG Electronics MRL1 Lock-Out Relay User Manual - cover page
Brand
SEG Electronics
Category
Industrial Supply
Document type
User Manual
Language
English
Pages
16
File format
PDF
File size
964 KB
Published
19 October, 2026
Updated
19 October, 2026
MD5 checksum
CDA9944C8ADA6CA15606E121148ED4C7

About this manual

The SEG Electronics MRL1 is a High Tech Line lock-out relay designed to manage tripping contacts when the available capacity of a protection relay is insufficient. It features manual, electrical, or automatic reset options and supports both high and low burden modes to prevent malfunctions caused by induced currents in long-distance lines.

The document provides detailed instructions on connecting the auxiliary voltage, testing tripping circuits, and utilizing the external reset input. It also lists comprehensive technical data, including supply voltage ranges, breaking capacities for AC and DC, and environmental specifications such as temperature limits and protection degrees.

What's inside

  • Summary and Application
  • Characteristics and Features
  • Function
  • Testing the relay and commissioning
  • Terminal block
  • Technical Data
  • Order form

Specifications

Supply voltage range (24 V DC)18 – 32 V
Supply voltage range (220 V DC)150 V – 300 V
Output contacts8 changeover contacts
Breaking capacity AC2650 VA/max. 400 V = 10 A
Breaking capacity DC (Ohmic)24 V/5A
Response time7 - 10 ms
Operating mode HB power consumption3.8 W at 24 V
Ambient service temperature limits-10°C to +55°C
Degree of protection (Front panel)IP40

Frequently asked questions

How can the MRL1 be reset?

The MRL1 can be reset manually using the Reset key, electrically via input terminals A5/E9, or automatically if the Auto-Reset coding plug is installed.

What is the difference between High Burden (HB) and Low Burden (LB) modes?

HB mode includes a high burden to prevent malfunctions from induced currents, consuming 150W, while LB mode is for lines without interference, consuming 50W.

What is the maximum tripping time of the relay?

The tripping time is less than or equal to 10 ms.

Can the MRL1 be used for automatic reset?

Yes, automatic reset is activated by plugging in the coding plug located behind the front plate.

Download PDF (964 KB)