Microcell™ Installation Manual, introduces the installation and use of Microcell™ system, including pre-check, installation steps, connection method, inspection method, etc.
This Kistler-Morse Microcell Installation Manual (97-1012-02, Revision G) provides instructions for installing the Microcell bolt-on strain gage sensor system on storage vessels. The Microcell detects strain changes in a vessel’s metal support structure and produces a voltage output proportional to weight changes.
The manual covers pre-check procedures, installation on vertical column legs and horizontal beams, junction box mounting and wiring, system calibration, troubleshooting, specifications, glossary, and spare parts recommendations.
| 3” Microcell resistance (white to red) | 8,300Ω - 8,700Ω |
|---|---|
| 2” Microcell resistance (white to red) | 1,800Ω - 2,200Ω |
| 3” Microcell stress limit | 2,500 psi - 7,500 psi |
| 2” Microcell stress limit | 3,750 psi - 11,250 psi |
| No-load output | +25mV to -25mV |
It is a highly sensitive bolt-on strain gage sensor.
The no-load output should be between +25mV and -25mV.
Use Sikaflex 1A polyurethane sealant or Dow Corning RTV 738 or RTV 739 only.