Neo-Dyn 182P Adjustable Vacuum Switch Installation and Operation Manual

This manual provides instructions for the use, installation, and maintenance of the Neo-Dyn 182P adjustable vacuum switch


Neo-Dyn 182P Adjustable Vacuum Switch Installation and Operation Manual - cover page
Brand
Neo-Dyn
Category
switch
Document type
User Manual
Language
English
Pages
16
File format
PDF
File size
77 KB
Published
26 October, 2023
Updated
26 October, 2023
MD5 checksum
C040E3FEF1EF7BD206387134FCDEEF69

About this manual

This manual covers the Neo-Dyn 182P adjustable vacuum switches, including Enclosure 6N for explosive atmospheres and Enclosure 3X for weatherproof applications. The switches are electromechanical sensing devices for pneumatic and hydraulic systems up to 150 psig; Enclosure 6N units are for Zone 1 potentially explosive atmospheres and Division 1 hazardous locations.

The document explains installation, process media compatibility, electrical connections, set-point adjustment, troubleshooting and specifications. It states that installation must be performed by a qualified electrician, describes the ¼” - 18 NPT male process connection, and covers adjustment using an adjustment nut inside the pressure port.

What's inside

  • Introduction
  • Customer Service
  • Other Configurations
  • Installation
  • Mounting and Process Connection
  • Process Media
  • Potentially Explosive Atmospheres (Hazardous Locations) Enclosure 6N Only
  • Electrical Connections
  • Adjustments
  • Troubleshooting

Specifications

Standard Pressure Port¼” - 18 NPT male
Conduit Connection½” - 14 NPT male
Shipping WeightApproximately 13 ounces (0.34 kg)
Standard Switching RatingUp to 11 A at 125 or 250 VAC; 5 A resistive at 28 VDC; 0.5 A resistive at 125 VDC
M Option Current Rating1 amp
Ingress ProtectionIP 66
Application RangePneumatic and hydraulic systems up to 150 psig

Frequently asked questions

How do I adjust the vacuum set point?

Remove the pressure connection, then use a 3/32 Allen wrench to turn the adjustment nut clockwise to increase the set point or counterclockwise to decrease it.

How can I check the increasing vacuum set point?

Connect a vacuum source and a calibrated pressure gauge or transducer, then slowly apply increasing vacuum until the switch actuates.

What is the standard process connection?

The switch’s process connection is ¼” - 18 NPT male.

What are the standard electrical leads?

Standard leads are 18 AWG free leads, 18 in (46 cm) long, with a green wire grounded to the case.